Installing Vent/ Combustion Air & Condensate7. Continue the pipe from the drain assemblyto a floor drain or condensate pump.NOTICEWhen selecting and installing a condensatepump, ensure the pump is approvedfor use with condensing boilers and furnaces.The pump should be equippedwith an overflow switch to prevent propertydamage from potential condensatespillage.CAUTIONThe condensate drain must remain filledand unobstructed and allow unrestrictedflow of condensate. The condensateshould not be subject to conditionswhere freezing could occur. If the condensateis subjected to freezing orbecomes obstructed , it can leak, resultingin potential water damage to theboiler and surrounding area.8. The PRESTIGE Solo will typically producea condensate that is considered slightlyacidic with a pH content below 3.0. Installa neutralizing filter if required by authorityhaving jurisdiction.Fill Plugwith VaccumBreak PortHeat ExchangerCondensateDrain NippleCompressionNut with Rubber SealRetaining Nutwith Rubber Seal(Hand Tight Only)Plastic BallFlexible Tubing(or 3/4 PVC/CPVC Pipingto Drain)CondensateDrain AssemblyFig. 15: Condensate Drain Assembly26