Outdoor Reset Control180Boiler Temperature ( F)140100866020Parameter 10Set PointParameter 12 SettingParameter 4 Set PointParameter 11 Setting90706450 30 10 0 -10Outdoor Air Temperature ( F)Graph 1: Outdoor Air Temperature Reset Curve (Example)Table 3: Outdoor Air Temperature Reset (Example)Graph 1 illustrates Parameter 4 adjusted to 140ºF target temperature at 0ºF outdoorair temperature.Note: Factory setting of Parameter 4 is 186ºF.53