8.4 Connecting asingle <strong>Stratos</strong>-<strong>HSSD</strong>-2to an addressable FirePanelAn APIC may be used to decode detector status information and relay this the the FirePanel via the Addressable Bus 1 and Bus 2 terminal block connections (see section 5.3.1‘Detector terminal block connections’).Addressable loopAddressablefire panelUniversaladdressableinterfaceStart address: 1End address: 1Detector 1NB ☞Note: The detector address on the RS485 communications loop and the Fire Paneladdressable protocol address are the same i.e. no address translation is performed.Some protocols may not support all of the available alarm levels and fault reporting isusually a general fault with no detailed fault information.8.5 Connectingto a PCTo connect a single stand-alone detector to a PC, connect the PC‘s serial port directlyto the detector‘s 9-way RS232 port. Connections for this cable are shown below.9 pin female ‘D‘connector235789 pin female ‘D‘connector32587Page 43<strong>Stratos</strong> <strong>HSSD</strong>-2 • INSTALLER’S <strong>HANDBOOK</strong> • Iss. 10© AirSense Technology. 2009