<strong>Water</strong> Facilities Master <strong>Plan</strong><br />
Existing <strong>Water</strong> <strong>Supply</strong> Facilities<br />
A 3-2<br />
KM2740.Sec3.doc<br />
11/26/2007<br />
3.1.2.2 John E. Preston Wellfield<br />
The seven active wells located in the John E. Preston Wellfield were constructed in<br />
1966 and 1972. Each well is 42 inches in diameter, 107 feet deep and have casing<br />
depths <strong>of</strong> 66. The capacity <strong>of</strong> wells No. 1 through No. 6 is 5,000 gallons per minute<br />
(gpm) each and the capacity <strong>of</strong> well No. 7 is 7,000 gpm. The total wellfield capacity is<br />
53.28 mgd.<br />
Table 3-1: Wellfield Data<br />
Wellfield Data<br />
Wellfield<br />
Hialeah-Preston<br />
Installed Design Capacity<br />
(mgd)<br />
Number <strong>of</strong> Wells<br />
Preston 53.28 7<br />
Hialeah 12.54 3<br />
<strong>Miami</strong> Springs 79.30 20<br />
Northwest (a) 149.35 15<br />
Subtotal 294.47 45<br />
Medley Wellfield (b) Alexander Orr<br />
43.20 4<br />
Orr <strong>Plan</strong>t 74.40 10<br />
Snapper Creek 40.00 4<br />
Southwest 161.16 17<br />
West 32.40 3<br />
Subtotal<br />
Existing South Dade<br />
307.96 34<br />
Elevated Tank 4.32 2<br />
Everglades Labor Camp 4.18 3<br />
Leisure <strong>City</strong> 6.12 4<br />
Naranja 1.15 1<br />
Newton 4.32 2<br />
Subtotal<br />
Proposed South <strong>Miami</strong> Heights<br />
20.09 12<br />
Caribbean Park 3.00 2<br />
Former <strong>Plan</strong>t 3.00 1<br />
Roberta Hunter Park 10.50 7<br />
Rock Pit Park (Future) N/A 2<br />
Subtotal 16.50 12<br />
MDWASD System Total 639.02 103<br />
(a) Northwest wellfield capacity at 150 mgd when pumps operate at low speed.<br />
(b) Wells in this wellfield had been abandoned. They were recently restored with the<br />
purpose <strong>of</strong> using them only during an emergency<br />
Source: MDWASD Draft Wellfield Operational <strong>Plan</strong>, 2007