OPERATIONAL RESTRICTIONSThe following conditions are not recommended, and may result in impaired operation of thesystem component.Proximity Card Readers• All Software House RM reader series products can be installed on metal surfaces. Somethird-party readers, such as HID ProxPro Plus, may exhibit reduced performance whenmounted near a metal object. Consult the installation guide or users’ manual for each specificproduct.• Performance may also degrade if the reader is exposed to any Radio Frequency fields withfrequencies near 125 KHz or 13.56 MHz.• The cable used to connect a Wiegand reader must not exceed 500 ft.Magnetic Stripe Readers• Performance may degrade or the unit stops working if installed near magnetic sources, suchas a motor.• The cable used to connect a magnetic read head must not exceed 10 ft.Note: In general, do not run reader cabling near high voltage lines or motorized equipment, suchas elevators or compressors.SUPPORTED/UNSUPPORTED FEATURESIN C•CURE 800/8000 VERSION 9.3Table 8 shows the features that were evaluated by <strong>UL</strong>.Table 8. Features Evaluated by <strong>UL</strong>FeatureEvent/Alarm MonitoringDoor ControlElevator ControlTime SpecificationsTime Zone ManagementOperator Privileges<strong>UL</strong> TestedYesYesYesYesYesYesC·CURE 800/8000 V9.4 <strong>UL</strong> <strong>Addendum</strong>13