UL Addendum - Tyco Security Products
UL Addendum - Tyco Security Products
UL Addendum - Tyco Security Products
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Network ConfigurationThe "<strong>UL</strong> Listed Encrypted Line <strong>Security</strong> Configuration" [2412-2274-01 A0] drawing shows asample wiring diagram for the Software House Router <strong>UL</strong> Test Configuration.• The Software House Model 0101-0181-01 encryption device and iStar Pro control panelmust be installed in the same room.• SWH Model 0101-0181-01 must be powered by a power supply evaluated to <strong>UL</strong> 603 or <strong>UL</strong>1481 with an output range within 10.7 and 29.0 VDC, and provides 2 A continuous and aminimum 4 hours of standby power.• Ethernet connections must be protected by the American Power Conversion Corporation(APCC), Model PNET1 surge suppressors. (See note 1 on the drawing.) Refer to the section"PNET1 Surge Suppressor" on page 40 for safety precautions and installation instructions.• The AC input for the Software House Router Model 0101-0180-01 must be protected by theAmerican Power Conversion Corporation APCC, Model P4 power line surge suppressor.(See note 3 on the drawing.) Refer to section "APCC P4" on page 42 for safety and powerinformation.<strong>UL</strong> Listed Encrypted Line <strong>Security</strong> Configuration [2412-2274-01 A0]C·CURE 800/8000 V9.4 <strong>UL</strong> <strong>Addendum</strong>39