Outputs Open collector, +12V DC, 0.5AReaders: RM1-PH, RM2-PHInput powerSignal Inputs+12V DC, +/-5%, 250mAClass A Supervised, 0 - 14,000 ohmsOutputs Open collector, +12V DC, 0.5AReaders: RM2L-PHInput powerSignal Inputs+12V DC, +/-5%, 250mAClass A Supervised, 0 - 14,000 ohmsOutputs Open collector, +12V DC, 0.5AReaders: RM3-PHInput powerSignal Inputs+12V DC, +/-5%, 250mAClass A Supervised, 0 - 14,000 ohmsOutputs Open collector, +12V DC, 0.5AReaders: RM1-WInput powerSignal Inputs+12V DC, +/-5%, 80mAClass A Supervised, 0 - 14,000 ohmsOutputs Open collector, +12V DC, 0.5ACabling and WireNote: All external connections (relays, battery wires, power supply wires, readers, etc.) must bemade to power limited circuits only. All cabling and wire used must be <strong>UL</strong> Listed and/orRecognized wire and must be suitable for the application, as described below.Wiring Main Power To an iSTARThe iSTAR must be connected to a power limited main circuit. Cabling must be <strong>UL</strong> Listedand/or Recognized. Refer to the product label for power requirements. The connection procedureis shown in the following diagram.1. Attach the conduit for the wiring from AC main power to the knockout closest to the powersupply in the enclosure.C·CURE 800/8000 V9.4 <strong>UL</strong> <strong>Addendum</strong>23