BT08L005GB-01PACKAGED362 - 904CPHG - HOT GAS RE-HEATING COILThis option is recommended during the summer when dehumidification of the room is required. The flow of air toenter the room may contain a higher level of humidity than desired. The dehumidification process is used toreduce it. The air flow is first cooled in the treatment coil with separation of condensation.It is then freely post-heated to maintain the desired condition of comfort in the room served. The post-heating coilis located behind the treatment coil and is activated by drawing a flow of hot gas down the line from thecompressors through the action of a dedicated solenoid valve.The process starts working based on the humidity set-point established by the user.With respect to traditional devices, such as electrical heating elements or hot water coils, the use of the postheatingcoil does not consume any energy. It also lowers the condensation temperature, which provides twopositive effects: the power absorbed by the compressors is considerably reduced, and at the same time thecooling power is increased with greater EER.TREATMENT COILRE-HEATING COILHUMID AIRCOLD AIRTREATED AIRHUMIDITY PROBECONDENSATE DISCHARGECOMPRESSORSTO THE CONDENSERELECTRONIC EXPAN-SION VALVEThis option reduces the available static pressure (air side).40