BT08L005GB-01EERPACKAGED362 - 904PANELLINGThe need to improve access to the internal parts of the machine for theordinary maintenance and at the same time the need to give structuralstiffness and increase thermal insulation has brought to the adoption of"sandwich" type panels on all units. The roof and the structure of the airtreatment area are made with such panels with dual steel walls withpolyurethain foam and feature seal gaskets alongside the ledge. Thepanels are hinged and feature handles and closures with adjustableclamping.VERY HIGH EFFICIENCY AT PARTIAL LOADIn air conditioning projects, the choice of the unit is made based on the maximum load of the room to be served.In practice, over the course of the year these operating conditions are limited to short periods of time, whereasoperation at partial loads is the actual normal operating condition. The need to adapt the power provided to theload requested becomes essential in limiting energy consumption. This is why we have decided to couple twoscroll compressors of different power on a single refrigeration circuit, thus obtaining very high efficiency. Theelectronic control that the machine is equipped with divides compressor operation into three steps of power (1/3,2/3, 3/3). This limits the oscillation of the air temperature, and provides perfect adaptation to partial load, offeringsubstantial energy savings.9876% Working Time100%90%80%70%For 70% of thetime the load isunder 50%For 90% of thetime the load isunder 80%60%550%440%330%220%110%(1)(2) (3)0(1) (2) (3)0%
BT08L005GB-01PACKAGED362 - 904STANDARD UNIT SPECIFICATIONSCOMPRESSORScroll compressor complete with: overload thermal protection, high refrigerantdischarge temperature, rubber antivibration mounts, oil charge.A oil heater is automatically switched on at the compressor shut-down to preventoil dilution by the refrigerant.The compressors are connected in tandem on a single refrigerator circuit. Theyhave bi-phase equalization of the oil and are equipped with cut-off bibcocksA oil heater is automatically switched on at the compressor shut-down to preventoil dilution by the refrigerant.STRUCTUREThe basement is assembled with a painted galvanized steel frame. The internalstructure is made of “ALUZINK” bent galvanized steel . The alloy that protects theAluzink allow an excellent corrosion proofing thanks to the galvanic protectiontypical of the combination aluminium-zinc.PANELLINGPanels of the compressor panel in steel sheet metal, painted using polyesterpowders, colour RAL 9001 and covered on the inside with ashlared soundabsorbentmaterial.Sandwich panels in the air treatment section with dual walls in steel sheet metalwith polyurethane insulation (40 kg/m3), thickness of outer sheet metal 6/10 mmgalvanized and painted using polyester powders colour RAL 9001, polyurethanethickness with thermal conductivity coefficient 0.022W/mK, thickness of internalsheet metal 5/10 mm hot galvanized. The panel is also provided with a PVCprofile for thermal insulation and a EPDM rubber gasket that ensures the hermeticseal.All panelling can easily be removed to allow complete accessibility to internalcomponents.INTERNAL EXCHANGERDirect expansion finned exchanger, made from copper pipes in staggered rowsand mechanically expanded to the fin collars. The fins are made from aluminiumwith a corrugated surface and adequately distanced to ensure the maximum heatexchange efficiency.EXTERNAL EXCHANGERDirect expansion heat exchanger with braze welded stainless steel AISI 316plates and complete with external thermal/anti-condensation insulation, completewith water side differential pressure switch and water temperature control probe.FANSUPPLY FANCentrifugal fan with double intake, blades curved forward to achieve maximumperformance and silence. Statically and dynamically balanced as per standardsISO 1940 degree 6.3. Fastened to rubber anti-vibration devices. The screw, rotorand frame are made of galvanized sheet metal (semdzimir) the shaft is made ofC40 steel. Connection to electric motor with belt and pulleys.REFRIGERANT CIRCUITThe circuit is complete with:- refrigerant charge- sight glass with moisture indicator- high pressure switch- low pressure switch- filter dryer- electronic expansion valve- non-return valve- 4-way reverse cycle valve- liquid receiver- high pressure safety valve- low pressure safety valveFILTRATIONPleated filter for greater filtering surface, made up of galvanized plate frame withgalvanized and electric-welded protective mesh, and regenerable filtering mediamade from polyester fibre sized with synthetic resins. G4 efficiency according toCEN-EN 779 standard (Eurovent class EU4/5 - average efficiency 90.1% A-SHRAE 52-76 Atm). Self-extinguishing (resistance to fire class 1 - DIN 53438).For units up to size 452: additional filter G4 on the fresh air intake.- clean contacts for remote ON-OFF, cumulative alarm, fan status, compressorstatus, summer/winter mode- control keypad, including:display of the parameter indexdisplay of the set values and the error codesMENU button to jump to the main menuALARM button to access the alarm management functionsstatus button to display the status listunit operation or ventilation only selection buttonOn/Off and manual reset button for overload device activationUP and DOWN buttons to increase and decrease the valuesSelected function signal LEDCompressor timer / operation signal LEDRETURN FAN(Constructional configuration C)Centrifugal fan with double intake, blades curved forward to achieve maximumperformance and silence. Statically and dynamically balanced as per standardsISO 1940 degree 6.3. Fastened to rubber anti-vibration devices. The screw, rotorand frame are made of galvanized sheet metal (semdzimir) the shaft is made ofC40 steel. Connection to electric motor with belt and pulleys.External sectionHelical fans with shaped aluminium blades, directly coupled to the three-phaseelectric motor, with built-in thermal overload protection, minimum IP 54 construction.Mounted in aerodynamic housings to increase efficiency and minimise noiselevels, and fitted with safety grills.TESTUnit manufactured according to the ISO 9001 quality standards and subject tofunctional testing at the end of the production lineACCESSORIES- copper / copper evaporator coils- 2 rows hot water coil- modulating three-way valve- hot gas re-heating coil- Copper / copper hot gas re-heating coil- electrode boiler steam humidifier- water to waste evaporating wet-deck humidifier- Electric heaters.- Air quality sensor for CO2 p.p.m. control- Air quality sensor for CO2 and VOC p.p.m. control- bag filters section F7 class- High efficiency electrostatic filters additional section- differential pressure switch for dirty air filters- high and low pressure gauges- Active regeneration circuit on exhaust air- Plumbing assembly for loop with constant flow rate- Plumbing assembly for loop with variable flow rate- Plumbing assembly for system with disposable water- Antifreeze heater protection on the water side exchanger- Steel mesh filter on the water side (separately supplied accessories)- free-cooling with temperature comparison only (standard for version C)- free-cooling with independent comparison of temperature and absolute humidity- On/off motorized air outlet damper (only for B version)- Modulating air outlet damper (only for B version)- Disposal for inrush current reductionFans- Application with fabric ducts (only for C version)- high and low pressure gauges- smoke detector- phase monitor- power factor correction capacitors (cosfi > 0.9)- serial port RS485 with LONWORK protocol- serial port RS485 with MODBUS protocol- Remote control with remote microprocessor control (separately supplied accessories)TRAYCondensation collection basin in aluminium alloy 1050 H24 with anticondensationinsulation, welded and equipped with siphoned drain tubeELECTRICAL PANELthe electrical panel is situated inside the units and is accessed through a hingeddoor that is opened by a special keyThe Power Section includes:- main door lock isolator switch- compressor circuit breaker- compressor power supply remote control switch- fan motor thermal overload protection on air handlingcoil side- circuit breaker to protect auxiliary circuitmicroprocessor control section:- treated air temperature control- compressor overload protection and timer- centralised alarms with remote signalling- self-diagnosis system with immediate display of the error code- demand limit7