Fort Nelson NRRM BASIC MECHANICAL SECTION 15050<br />

Airport Terminal Building MATERIALS METHODS Page: 3<br />

Washroom Renovations<br />

LCD display with switch to display Celsius or Fahrenheit degrees and an adjustable angle stem.<br />

Thermometer shall require no external power, needing only 35 lux of illumination to operate.<br />

10. Provide liquid filled pressure gauges where indicated on drawings and as specified herein.<br />

Provide on each side of each hot water circulating pump a pressure gauge with needle type<br />

isolation valve. Gauge calibration shall be such that instrument indicates at approximately mid<br />

scale under normal operating conditions. Gauges shall be 100mm [4.0"] diameter face as<br />

manufactured by Miljoco, Trerice, or approved equal. Pressure gauges shall be calibrated in S.I.<br />

metric units, or have dual metric/imperial calibration.<br />

11. Provide installation of temperature control system components where required in piping system.<br />

12. Insulating dielectric fittings shall be installed between dissimilar metals in systems. Brass<br />

adapters and valves are not accepted as dielectric fittings.<br />

15061 PLUMBING PIPING<br />

1. Water supply piping shall be hard copper type "L" in building, with solder joints. Underground<br />

piping shall be soft copper type "K" with wrought copper fittings and silver solder. Copper<br />

water tubing shall be certified by Warnock Hersey or Canadian Standards Association to ensure<br />

compliance with the B.C. Plumbing Code which references ASTM B88-83A. Water supply<br />

piping under concrete slabs or in walls shall be encased in standard weight flexible polyethylene<br />

pipe one size larger than copper tubing. All joints to be wrapped with Polyken tape. The use of<br />

Victaulic copper connection system is acceptable. Couplings to utilize angle bolt pad design<br />

Style 606 with EPDM flush seal gasket.<br />

2. Water service pipe 150mm (6") or larger in building shall be Ductile Iron, minimum Pressure<br />

Class 350 designed and manufactured in accordance with ANSI/AWWA C150/A21.50 and<br />

C151/A21.51. All pipe shall be cement-mortar lined in accordance with ANSI/AWWA<br />

C104/A21.4 and grooved to BS 4772/ISO 2531 standards to accept Victaulic fittings. Fittings<br />

shall be British Standard/ISO cement-mortar lined and bituminous coated ductile iron fittings<br />

conforming to ASTM A-536 with Grade “M” FlushSeal gaskets suitable for a temperature range<br />

of -20 F to + 200 F. Bolts and nuts shall be heat treated, plated carbon steel.<br />

3. Water supply piping exposed in finished areas shall be chrome plated brass pipe and fittings.<br />

4. Underground drainage piping under building or paved areas shall be mechanical joint cast-iron<br />

soil pipe. Specified piping materials and applications shall be in accordance with B.C. Building<br />

Code 2006, Part 7, Plumbing Services.<br />

5. Drainage and vent piping within the building shall be either DWV copper or cast iron at the<br />

Contractor's option, provided adequate space is available for drainage piping installation without<br />

allowing direct contact between piping and structure. Copper drainage and vent piping in<br />

masonry walls shall be Polyken tape wrapped if un-insulated.<br />

February 2012 JM BEAN & CO. LTD 1130.10