Fort Nelson NRRM PLUMBING SECTION 15400<br />

Airport Terminal Building Page: 2<br />

Washroom Renovations<br />

8. Provide floor drains with lead flashings, clamping device and chrome plated strainers with<br />

diameter twice as great as drainage connections.<br />

9. Provide roof drains with flashing and strainers of size indicated. Roof drain installations shall<br />

be made in accordance with recommendations of Canadian Roofing Contractors Association.<br />

10. Lines and Grades:<br />

Lay piping true to line and grade; fit ends together, match so that sewer or drain will have<br />

smooth and uniform invert throughout its length.<br />

11. Minimum Cover:<br />

Maintain 762m [30"] minimum cover above piping or bury below frost line in accordance with<br />

local practice, whichever is greater. Where piping is indicated as connecting to or crossing over<br />

piping, determine elevations of such lines before proceeding with new piping installation. In<br />

shop drawing show necessary re-routing to avoid interferences, submit for approval before<br />

proceeding with this work.<br />

12. When trench has been excavated to required depth, test bottom to determine its suitability for<br />

pipe support. If rock is encountered excavate to depth of 150mm [6"] below pipe bottom and<br />

fill this space and other irregularities with tamped sand before pipe is laid.<br />

15430 DRAINAGE SPECIALTIES<br />

1. Cleanouts:<br />

Cleanouts shall be installed in easily accessible locations near the foot of each soil stack, waste<br />

stack or rain water leader, and at each change in direction of building drain greater than 45°.<br />

The distance between cleanouts in horizontal lines shall not exceed 15.2m [50']. Cleanouts shall<br />

be of the same nominal size as the piping in which they are installed up to 100mm [4"] and not<br />

less than 100mm [4"] in size for larger piping. When installed at finished floor level cleanouts<br />

shall have countersunk heads in unfinished areas and access boxes and covers on finished floor<br />

areas. All cleanouts are to be installed so cleanout hub faces directly into access door.<br />

15440 PLUMBING FIXTURES & TRIM<br />

1. General<br />

Provide as indicated on Drawings as specified herein Plumbing Fixtures and Trim. Fixtures<br />

shall be as listed below under their appropriate symbol and similarly identified on the drawings.<br />

The following notes apply:<br />

(a)<br />

(b)<br />

(c)<br />

All catalogue numbers are "American Standard" unless otherwise indicated.<br />

All fixtures (except stainless steel) are to be white.<br />

Refer to Architectural Drawings for exact location of fixtures.<br />

February 2012 JM BEAN & CO. LTD 1130.10