Fort Nelson NRRM REFRIGERATION SECTION 15650<br />

Airport Terminal Building Page: 2<br />

Washroom Renovations<br />

and diagnostic codes to identify any problems. All codes shall be listed inside control access<br />

panel for easy reference.<br />

8. The unit shall have a fully modulating economiser section complete with outdoor air hood and<br />

pressure relief dampers (and hood). The economiser controls shall use the add-on Prodigy<br />

control board with the sensible control. Economizer shall be factory installed. The assembly<br />

shall include fully modulating 0-100 percent motor and dampers, barometric relief, minimum<br />

position setting, preset linkage, wiring harness with plug. The outdoor air damper shall return to<br />

a minimum position when outdoor temperature is too high for proper cooling. An adjustable<br />

minimum position damper switch shall position the outdoor air damper.<br />

9. Assemble units on roof; provide duct connections and accessories as indicated. Provide control<br />

wiring to and replace the existing programmable room thermostats with new wall mounted,<br />

programmable, auto-changeover thermostats and clear plastic guards. Arrange with the Owner<br />

for appropriate start and stop times to be programmed.<br />

10. Manufacturer or authorized representative shall provide field starting service for the units.<br />

Start-up air conditioning units in accordance with manufacturer’s start-up instructions. Test<br />

controls and demonstrate compliance with requirements. Provide start-up reports.<br />

Unit Schedule:<br />

AC - 2<br />

Model : LGH036H4ES_Y<br />

Supply Air Flow: 1000 CFM<br />

Gross Cooling (2 nd stage): 34,300 Btuh<br />

SEER / EER at ARI conditions: 17.0 / 12.5<br />

Heating input: 65,000 Btuh @ 80% AFUE<br />

Indoor blower HP: ½<br />

Electrical Characteristics: 208/230V, 3 Ph<br />

Minimum Circuit Ampacity: 23<br />

Weight (incl. accessories, wo/ curb): 716 lbs<br />

END of SECTION 15650<br />

February 2012 JM BEAN & CO. LTD 1130.10