Fort Nelson NRRM NOISE VIBRATION AND SECTION 15200<br />

Airport Terminal Building SEISMIC CONTROL Page: 4<br />

Washroom Renovations<br />

- Suppliers' detailed drawings of support/connection types, marked up to show loads or<br />

load ranges shall be used to facilitate type designations.<br />

- Referenced construction details, from "Guidelines" mentioned in .01 above, of<br />

support/connection types, marked up to show loads or load ranges may be used to<br />

facilitate type designations.<br />

12. Provide equipment restraints as manufactured by Mason Industries Inc. or approved equal.<br />

Shop drawings must clearly indicate recommended method of installation and points of<br />

attachment of hangers and supports to provide the necessary seismic restraint and be sealed by a<br />

B.C. registered Professional Engineer.<br />

- Shop drawings shall include statements detailing:<br />

●<br />

●<br />

●<br />

●<br />

Operating weight<br />

Calculated lateral force value V p<br />

Number of foundation bolts required and shear force on bolts.<br />

Tension force on anchorages from sum of moments for overturning.<br />

- It is equipment manufacturer's responsibility to design strength and anchorage of internal<br />

components that exceeds the force level required to restrain and anchor the unit to the<br />

supporting structure. Manufacturer's equipment shop drawings, required to be submitted<br />

for review prior to fabrication, shall certify that equipment construction complies with<br />

requirements of 2006 B.C. Building Code section 4.1.9.<br />

13. The vibration isolation/seismic restraint vendor shall provide all seismic restraint related<br />

hardware for fastening equipment, from point of attachment to equipment through to and<br />

including attachment to structure. All hardware required for seismically restraining hung<br />

equipment, piping and ductwork (excluding sprinkler systems and standard suspension hardware<br />

i.e. threaded rod and angle iron) shall also be provided by vibration isolation/seismic restraint<br />

vendor. Equipment suppliers shall provide appropriate holes, tabs, brackets, etc. to<br />

accommodate attachment of seismic restraint devices.<br />

14. For Fort Nelson, B.C. site the following values apply:<br />

Seismic Hazard Level (SHL) = C<br />

Lateral force, V p = v(S p )W p .<br />

Zonal velocity ratio, v = 0.05<br />

Horizontal force factor, S p as defined in the Code for mechanical/electrical equipment.<br />

W p is weight of component(s) being considered.<br />

15. Provide the services of the Professional Engineer(s) who designed the restraint systems for<br />

"Field Review" of the installed components including completion of the Letters of Assurance of<br />

Professional Review and Compliance in accordance with the Building Code. Typewritten<br />

inspection reports shall be submitted to the project consultant during the construction period.<br />