Fort Nelson NRRM CONTROLS SECTION 15920<br />

Airport Terminal Building Page: 1<br />

Washroom Renovations<br />

15921 GENERAL<br />

1. Provide low voltage control wiring for packaged devices in strict accordance with<br />

Manufacturer's Installation Instructions. Arrange with and pay electrical sub-contractor for<br />

installation of empty conduit for thermostat locations or provide such conduit in exposed<br />

locations and in walls.<br />

2. The Control System shall be installed by the Control Contractor but as an integral part of the<br />

Mechanical Sub-contract. The system shall be installed by certified journeymen, electricians<br />

and registered electrical apprentices regularly employed by the Control Contractor.<br />

3. The system shall be tested, completely calibrated and adjusted prior to final inspection by the<br />

Engineer.<br />

4. All instrument calibrations and readouts shall include SI metric units, temperatures shall be in<br />

Celsius.<br />

15936 ELECTRICAL COMPONENTS, WIRING AND CONDUIT<br />

1. Provide:<br />

All control system components, except those supplied as part of packaged equipment controls,<br />

but including all auto sequencing devices, electric relays, safety devices and electrical interlocks<br />

required to accomplish specified sequences. Refer to the electrical motor schedule in the<br />

electrical drawings and/or specification, which delineate the limits of electrical work in Division<br />

16 (Electrical) serving mechanical systems.<br />

All control circuit transformers required for control systems and not supplied by Division 16<br />

including line voltage power connection from indicated outlets shall be included by Division 15.<br />

All wiring shall be copper with RW90 X-Link P.E. insulation #12 minimum size. Wiring is to<br />

be in conduit in all wall spaces and exposed locations as well as in pipe chases, service spaces,<br />

attics, and crawl spaces which are entered for service access. Wiring in suspended ceiling<br />

spaces does not require conduit but shall be neatly installed parallel to building lines using<br />

bridle rings. All wiring installed under this contract shall be plenum rated FT-6 or FT-4, if<br />

approved by all authorities having jurisdiction. Locate wiring away from top or bottom of<br />

ceiling joists or trusses to minimize possibility of accidental damage. Number 18 gauge wire<br />

may be used in Class 2 circuits unless voltage drops are excessive. THHN wire will not be<br />

acceptable. Twisted shielded wiring, minimum of 22 gauge wire shall be used for all DDC or<br />

co-axial communication wiring. Line voltage alternating current wiring shall not be run in the<br />

same conduit, or cabling as DDC wiring.<br />

Use 1m of flexible conduit for all connections to vibrating equipment. Use liquid tight flex cable<br />

and connections where required.<br />

February 2012 JM BEAN & CO. LTD 1130.10