Fort Nelson NRRM BASIC MECHANICAL SECTION 15050<br />

Airport Terminal Building MATERIALS METHODS Page: 5<br />

Washroom Renovations<br />

All valves 75mm (3") and larger shall be at least 200 psi cold working pressure rating marked<br />

and approved equal to the following:<br />

Globe Valves Crane 351 Jenkins 2342J Red-White 400A Kitz 76<br />

Gate Valves Crane 461 or 460 Jenkins 451J or 452J Red-White 415A Kitz 5<br />

Check Valves Crane 373 or 372 Jenkins 588J or 587J Red-White 435A Kitz 78<br />

Check Valves Crane 383 Jenkins 477LJ Red-White 435A Kitz 78<br />

Sewage Valves Crane 383 OL & W<br />

Butterfly Valves<br />

(Gear Operated)<br />

Victaulic No. 608<br />

Mueller<br />

Locxend Model<br />

89G<br />

Red-White<br />

918BESL<br />

Drain and hose valves 20mm (3/4") and smaller shall be the following or approved equal:<br />

Sediment Faucets Emco 10740<br />

Drain valves Crane F9202/Jenkins 201J c/w ball & chain Red - White 5046 Kitz 68AC<br />

12. Expansion joints shall be Flexonics Model HB suitable for 1034 kPa (150 psi) working pressure<br />

and 50mm (2") traverse.<br />

13. Strainers 50mm (2") and smaller shall be Red & White Bronze Fig. No. 380E. Kitz 15<br />

Larger strainers shall be Red & White Bronze Fig. No. 381A. Kitz 80 or Mueller 351M<br />

15062 UNDERGROUND PIPE AND FITTINGS (NOT IN CONTRACT (NIC) )<br />

1. Underground water pipe shall be PVC pipe conforming to AWWA Standard C900-75 "Poly<br />

(Vinyl Chloride) (PVC) Pressure Pipe 4 through 12 inch (100 through 300mm) for water", CSA<br />

B137.3 ULC CEx448, and UNI-B-3-80. The pipe is to be Class 150psi (Dimensional Ratio<br />

(DR)-18 with cast iron outside diameter) and integral bell gasket joint. Gaskets are to be<br />

bonded into the ring groove prior to shipment. Underground fittings shall have joints and<br />

pressure rating compatible with pipe used.<br />

2. Provide underground gate valves where indicated. Valves shall be equal to Mueller double disc<br />

or Mueller resilient seated type, NRS style, installed with Dobney Foundry Nelson Type valve<br />

box at grade to permit easy operation. Valves shall conform to the applicable Municipal<br />

Standards for pressure rating and type.<br />

3. All underground piping for fire mains shall be installed, clamped and anchored and flushed and<br />

hydrostatically pressure tested according to requirements of NFPA 13 and NFPA 24 latest<br />

Editions. Flushing shall be done through 100mm (4") minimum diameter piping. Continuously<br />

threaded rod shall not be used for underground applications.<br />

February 2012 JM BEAN & CO. LTD 1130.10