Fort Nelson NRRM BASIC MECHANICAL SECTION 15050<br />

Airport Terminal Building MATERIALS METHODS Page: 10<br />

Washroom Renovations<br />

be set in structural members of the building to the Architect's approval. Pipe hangers shall be<br />

Grinnell Fig. 260, adjustable wrought clevis, Fig. 101 adjustable swivel ring, solid ring Type or<br />

Fig. 237 steel band and bolt. Perforated band iron, wire or chain hangers will not be approved.<br />

All hangers for copper pipe shall be copper, copper clad or use plastic-tape wrapped pipe at<br />

hanger. Inserts shall be Grinnell Fig. 152.<br />

3. All hangers shall be capable of vertical adjustment after pipe is erected. Pipe shall not be hung<br />

from other pipe.<br />

4. All insulated pipe 50mm [2"] and larger shall be fitted with insulation protection saddles, or<br />

insulation protection shields.<br />

5. On all pipe with vapour-seal insulation the hanger shall fit outside the insulation. Provide Fig.<br />

167 insulation protection shields on all insulated cold piping such as domestic water, chilled<br />

water and rain water leaders so that hanger rod and pipe hanger will not penetrate insulation<br />

vapour barrier.<br />

6. Pipe hanger rods shall be continuously threaded, cadmium plated and shall be sized and spaced<br />

as follows:<br />

PIPE DIA<br />

(inches)<br />

HANGER<br />

ROD DIA.<br />

(inches)<br />

MAXIMUM HANGER SPACING<br />

STEEL<br />

SCH.40<br />

(feet)<br />

COPPER<br />

DWV,L,K<br />

(feet)<br />

CAST.I<br />

STD.<br />

(feet)<br />

GLASS<br />

(feet)<br />

PLASTIC<br />

DWV,SCH.40<br />

(feet)<br />

1/2" 1/4" 6' 6' 4'<br />

3/4" & 1" 1/4" 8' 6' 4'<br />

1¼" 3/8" 10' 6' 4'<br />

1½" 3/8" 10' 6' 10' 4'<br />

2" 3/8" 10' 10' 10' 4'<br />

2½", 3 & 4" 1/2" 10' 10' 10' 8' 4'<br />

5", 6" & 8" 5/8" 10' 10' 10' 8' 4'<br />

February 2012 JM BEAN & CO. LTD 1130.10