• Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X /<br />

type 4X / NEMA 6, IP67, IP68 locations.<br />

• The maximum input voltage to the barrier must not exceed 250 V rms.<br />

• Recommended intrinsically safe barriers are listed on page 9.<br />

• Refer to Instructions specific to hazardous area installations on page 10.<br />

EU Equivalency (barrier selection)<br />

Any zener diode safety barrier, certified by an EU approved certification body to [ EEx ia ] IIC,<br />

its output voltage (U o ) not exceeding 30 V and its output current (I o ) limited by load resistance<br />

(R o); such that I o = U o / R o, does not exceed 120 mA.<br />

IS Safety Barrier Selection<br />

Selecting a suitable barrier or power supply requires knowledge about Intrinsic Safety and the<br />

application. It is the responsibility of the installer to ensure that the intrinsically safe<br />

installation complies with both the apparatus approval requirements and the relevant national<br />

code of practice.<br />

How to select a passive barrier for <strong>SITRANS</strong> <strong>LR200</strong><br />

1. Make sure that the barrier safety description is suitable for the <strong>LR200</strong> Intrinsically Safe<br />

(IS) input parameters.<br />

2. Determine the maximum end-to-end resistance of the barrier (Re-e) from the data sheet.<br />

3. Determine other loop resistance (Rloop): for example, sense resistance, displays, and/or<br />

PLC inputs.<br />

4. Calculate Rworking = Re-e + Rloop.<br />

5. Determine any non-linear voltage drops due to the barrier (Vbarrier) from the barrier data<br />

sheet (for example, voltage drops due to diodes).<br />

6. Calculate Vworking = Vsupply – Vbarrier.<br />

7. Using Vworking and Rworking, confirm that operation is within the shaded area of the<br />

graph Loop Voltage versus Loop Resistance on page 5 of Appendix A.<br />

Notes:<br />

• The following list is not complete: there are many safety barriers on the market, which<br />

will work with the <strong>LR200</strong>.<br />

• The barriers listed below have all been tested and are functionally compatible with the<br />

LR 200.<br />

• The barriers listed below are all <strong>HART</strong> compatible.<br />

PLC Input Modules<br />

Manufacturer Part Number<br />

<strong>Siemens</strong> SM331 PCS7 <strong>HART</strong> Input Module<br />

7ML19985QL83 <strong>SITRANS</strong> <strong>LR200</strong> (<strong>HART</strong>) – QUICK START MANUAL Page EN-9<br />