Rod Assembly (PTFE rod antenna version only)<br />
Wiring<br />
Power 1<br />
Optional<br />
Extension 100 mm (4")<br />
50 mm (2”)<br />
PTFE paste is supplied with<br />
PTFE rod antenna versions<br />
(non-sanitary type).<br />
WARNINGS:<br />
DC terminals shall be supplied from an SELV 1 source in accordance with IEC-<br />
1010-1 Annex H.<br />
All field wiring must have insulation suitable for rated voltages.<br />
Connecting <strong>SITRANS</strong> <strong>LR200</strong> 2<br />
Notes:<br />
• Water or process fluids must not enter the<br />
connecting threads: this could cause reflections at<br />
the connection, which will appear as false echoes.<br />
• Apply a small amount of PTFE paste to the antenna<br />
threads before threading the antenna together, and<br />
tighten slowly. Ensure that the rod sections mate<br />
securely with no gaps. Do not apply too much PTFE<br />
paste or the parts will not mate securely.<br />
• Do not use wrenches or pliers. Hand tighten only<br />
(except in pressure applications: see warning<br />
above).<br />
WARNINGS:<br />
Check the nameplate on your instrument, to verify the approval rating.<br />
Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X<br />
/ type 4X / NEMA 6, IP67, IP68 locations.<br />
Read Instructions specific to hazardous area installations on page 10.<br />
Notes:<br />
• For detailed wiring instructions, please refer to the full Instruction <strong>Manual</strong>.<br />
• Use shielded, twisted pair cable: AWG 22 to 14 (0.34 mm 2 to 2.5 mm 2 ).<br />
• Separate cables and conduits 2 may be required to conform to standard instrumentation<br />
wiring practices, or electrical codes.<br />
1. Safety Extra Low Voltage<br />
2. If cable is routed through conduit, use only approved suitable-size hubs for waterproof application.<br />
Page EN-6 <strong>SITRANS</strong> <strong>LR200</strong> (<strong>HART</strong>) – QUICK START MANUAL 7ML19985QL83