5.7 <strong>Installation</strong> of the fuel system<br />
Camino Generators<br />
<strong>Installation</strong> of the fuel system can be adapted to the local conditions. Follow the<br />
specifically described specification when operating it via the vehicle fuel s<strong>up</strong>ply system.<br />
The separately working fuel s<strong>up</strong>ply system consists of the following:<br />
1. Fuel tank<br />
2. Shut-off cock*<br />
3. Electrical fuel delivery pump<br />
4. Non-return valve*<br />
5. Water separator with fine filter*<br />
6. S<strong>up</strong>ply line<br />
7. Return line<br />
*not required in any case<br />
If a Diesel tank is used with was not delivered with the system, use a<br />
design approved Diesel tank type. If using a common Diesel fuel tank<br />
with the main engine, install an independent connection for the generator<br />
with foot-operated valve <strong>and</strong> ball valve.<br />
All components <strong>and</strong> hoses used must be suitable for Diesel fuel. Install<br />
hose lines at a fire-resistant base<br />
All metal components <strong>and</strong> lines of the fuel system must be connected<br />
with each other via an equipotential bonding system.<br />
03-04-01 <strong>Installation</strong> of the SET Camino Generator 5-41