Camino Generators<br />

4. Connect the s<strong>up</strong>ply line (4) via Diesel free pipelines/fuel hose NW8 <strong>and</strong>...<br />

− non-return valve* (5) (...prevents the fuel from returning <strong>and</strong> thus draining of<br />

the s<strong>up</strong>ply line)<br />

− shut-off valve ¼“ * (6)<br />

− electrical fuel delivery pump* (7) (...to be mounted near the Diesel tank)<br />

− water separator* (8) direct downstream of the electrical fuel delivery pump.<br />

Leave sufficient space for filter replacement/cleaning. (From SET range of<br />

accessories)<br />

to the connection line (9) of the SET Camino Generator.<br />

* (refer also to the documents of sub-s<strong>up</strong>pliers)<br />

The end of the return line shall end slightly above the tank bottom.<br />

Thus the line end is always filled with fuel <strong>and</strong> the lines are prevented<br />

from draining.<br />

Prior to <strong>start</strong> <strong>up</strong> <strong>and</strong> on completion of assembly check the whole fuel<br />

system for leaks.<br />

03-04-01 <strong>Installation</strong> of the SET Camino Generator 5-43