Wrong orientation to the product<br />
Weak measuring signals are generated if the<br />
sensor is not directly pointed at the product<br />
surface. Orient the sensor axis perpendicularly<br />
to the product surface to achieve optimum<br />
measuring results.<br />
Correct Incorrect<br />
Ladder<br />
Direct sensor vertically to the product surface<br />
Sensor too close to the vessel wall<br />
If the radar sensor is mounted too close to<br />
the vessel wall, strong false echoes can be<br />
caused. Buildup, rivets, screws or weld joints<br />
superimpose their echoes onto the product<br />
i.e. useful echo. Please ensure a sufficient<br />
distance from the sensor to the vessel wall.<br />
Sensor too close to the vessel wall<br />
Ladder<br />
If there are good reflection conditions (liquid<br />
medium, no vessel installations), we recommend<br />
locating the sensor where there is no<br />
vessel wall within the inner emission cone. For<br />
products in less favourable reflection environments,<br />
it is a good idea to also keep the<br />
outer emission cone free of interfering installations.<br />
Note chapter "4.1 General installation<br />
instructions“.<br />
Foam generation<br />
Thick, dense and creamy foam on the product<br />
can cause incorrect measurements. Take<br />
measures to avoid foam, measure in a bypass<br />
tube or use another measuring technology,<br />
e.g. capacitive meas. probes or<br />
hydrostatic pressure transmitters.<br />
Foam generation<br />
Mounting and installation<br />