SIL declaration of conformity<br />

S I L d e c l a r a t i o n of c o n f o r m i t y<br />

Functional safety according to IEC 61508 / IEC 61511<br />

VEGA Grieshaber KG, Am Hohenstein 113, D-77761 Schiltach<br />

declares as manufacturer, that for the radar sensors of the product families<br />

<strong>VEGAPULS</strong> series 40 and 50 ( 4 ... 20 mA HART® )<br />

Füllstand - Grenzstand - Druck<br />

the reliability (“proven in use”) was verified according to IEC 61508 / IEC 61511.<br />

Therefore the devices are suitable for safety-related applications<br />

e.g. overfill protection, dry run protection or recording of an arbitrary fill level.<br />

The corresponding instructions of the safety manual must be considered. 1)<br />

Safety related characteristics:<br />

<strong>VEGAPULS</strong> 40 <strong>VEGAPULS</strong> 50<br />

SIL Safety Integrity Level SIL 2 SIL 2<br />

HFT Hardware Fault Tolerance<br />

2)<br />

0 0<br />

SFF Safe Failure Fraction > 88 % > 86 %<br />

< 0,10 x 10 -2 < 0,12 x 10 -2 PFDavg average Probability of dangerous<br />

Failure on Demand<br />

(for low demand mode)<br />

3)<br />

< 0,50 x 10<br />

TProof 1 year<br />

-2 < 0,60 x 10 -2 TProof 5 years<br />

PFH<br />

[1/h]<br />

Probability of a dangerous Failure per<br />

4)<br />

Hour<br />

(for high demand or continuous mode)<br />

< 0,22 x 10 -6 < 0,28 x 10 -6 Error response time<br />

60sec<br />

The failure rates were determined by a FMEDA ( Failure Modes, Effects and Diagnostics Analysis )<br />

<strong>VEGAPULS</strong> 40 <strong>VEGAPULS</strong> 50<br />

λsd safe detected failure 107 FIT 111 FIT<br />

5)<br />

λsu safe undetected failure 494 FIT 518 FIT<br />

λdd dangerous detected failure 1090 FIT 1140 FIT<br />

λdu dangerous undetected failure 221 FIT 277 FIT<br />

MTTF Mean Time To Failure 60 years 56 years MTTR = 8h<br />

1) Safety Manual see supplement of the operating instructions<br />

2) HFT is reduced by one according to IEC 61511-1, section 11.4.4<br />

3) PFDavg is valid only for the TProof interval according to which a recurring function test must be carried out<br />

4) PFH is constant over the time. According to the standard, a recurring function test is not necessary.<br />

The failure tolerance time of the overall system must be higher than the error response time of the sensor.<br />

5) FIT = failure in time [10 -9 h]<br />

The assessment of the modification management was part of the proof for reliability (“proven in use”).<br />

Schiltach, 28.10.03<br />

VEGA Grieshaber KG<br />

i.V. Frühauf i.A. Blessing<br />

Head of Certification department Commissioner for functional safety<br />

SIL-KE_PULS40+50_EN_031028<br />

Supplement<br />

52 <strong>VEGAPULS</strong> <strong>54K</strong> <strong>enamel</strong><br />

24 101-EN-041227