SIL declaration of conformity<br />
S I L d e c l a r a t i o n of c o n f o r m i t y<br />
Functional safety according to IEC 61508 / IEC 61511<br />
VEGA Grieshaber KG, Am Hohenstein 113, D-77761 Schiltach<br />
declares as manufacturer, that for the radar sensors of the product families<br />
<strong>VEGAPULS</strong> series 40 and 50 ( 4 ... 20 mA HART® )<br />
Füllstand - Grenzstand - Druck<br />
the reliability (“proven in use”) was verified according to IEC 61508 / IEC 61511.<br />
Therefore the devices are suitable for safety-related applications<br />
e.g. overfill protection, dry run protection or recording of an arbitrary fill level.<br />
The corresponding instructions of the safety manual must be considered. 1)<br />
Safety related characteristics:<br />
<strong>VEGAPULS</strong> 40 <strong>VEGAPULS</strong> 50<br />
SIL Safety Integrity Level SIL 2 SIL 2<br />
HFT Hardware Fault Tolerance<br />
2)<br />
0 0<br />
SFF Safe Failure Fraction > 88 % > 86 %<br />
< 0,10 x 10 -2 < 0,12 x 10 -2 PFDavg average Probability of dangerous<br />
Failure on Demand<br />
(for low demand mode)<br />
3)<br />
< 0,50 x 10<br />
TProof 1 year<br />
-2 < 0,60 x 10 -2 TProof 5 years<br />
PFH<br />
[1/h]<br />
Probability of a dangerous Failure per<br />
4)<br />
Hour<br />
(for high demand or continuous mode)<br />
< 0,22 x 10 -6 < 0,28 x 10 -6 Error response time<br />
60sec<br />
The failure rates were determined by a FMEDA ( Failure Modes, Effects and Diagnostics Analysis )<br />
<strong>VEGAPULS</strong> 40 <strong>VEGAPULS</strong> 50<br />
λsd safe detected failure 107 FIT 111 FIT<br />
5)<br />
λsu safe undetected failure 494 FIT 518 FIT<br />
λdd dangerous detected failure 1090 FIT 1140 FIT<br />
λdu dangerous undetected failure 221 FIT 277 FIT<br />
MTTF Mean Time To Failure 60 years 56 years MTTR = 8h<br />
1) Safety Manual see supplement of the operating instructions<br />
2) HFT is reduced by one according to IEC 61511-1, section 11.4.4<br />
3) PFDavg is valid only for the TProof interval according to which a recurring function test must be carried out<br />
4) PFH is constant over the time. According to the standard, a recurring function test is not necessary.<br />
The failure tolerance time of the overall system must be higher than the error response time of the sensor.<br />
5) FIT = failure in time [10 -9 h]<br />
The assessment of the modification management was part of the proof for reliability (“proven in use”).<br />
Schiltach, 28.10.03<br />
VEGA Grieshaber KG<br />
i.V. Frühauf i.A. Blessing<br />
Head of Certification department Commissioner for functional safety<br />
SIL-KE_PULS40+50_EN_031028<br />