24 101-EN-041227<br />
Electrical connection<br />
Version with aluminium housing<br />
4 … 20 mA passive<br />
+ -<br />
1)<br />
Two-wire technology<br />
(loop powered)<br />
To the indicating instrument in the<br />
sensor lid or to the external indicating<br />
instrument VEGADIS 50<br />
1 2 C 3 4 5 6 7 8<br />
1 2 C 3 4 5 6 7 8<br />
(+) (-)<br />
L1 N<br />
Commu- +-<br />
nication 4...20mA Display<br />
-<br />
+<br />
ESC ESC<br />
OK OK<br />
M20 x 1.5<br />
(diameter of the<br />
connection cable<br />
5…9 mm)<br />
1) 4 … 20 mA passive means that the sensor<br />
consumes a level-dependent current of 4 … 20 mA<br />
(consumer).<br />
Sockets for connection<br />
of<br />
VEGACONNECT<br />
(communication<br />
sockets)<br />
Four-wire technology<br />
4 … 20 mA active<br />
+ -<br />
Voltage supply<br />
+ -<br />
2)<br />
To the indicating<br />
instrument in the sensor<br />
lid or to the external<br />
indicating instrument<br />
M20 x 1.5<br />
(diameter of<br />
the connection<br />
cable<br />
VEGADIS 50<br />
6…9 mm) M20 x 1.5<br />
1 2 C 3 4 5 6 7 8<br />
1 2 C 3 4 5 6 7 8<br />
<strong>VEGAPULS</strong> <strong>54K</strong> <strong>enamel</strong> 17<br />
(+) (-)<br />
L1 N<br />
Commu- +-<br />
nication 4...20mA Display<br />
-<br />
2) 4 … 20 mA active means that the sensor provides<br />
a level-dependent current of 4 … 20 mA (current<br />
source).<br />
+<br />
ESC ESC<br />
OK OK