Supplement<br />
3 Set-up<br />
3.1 Mounting and installation<br />
The prevailing plant conditions influence the safety of the measuring system. Therefore note<br />
the mounting and installation instructions of the appropriate operating instructions manual.<br />
3.2 Adjustment instructions and parameter settings<br />
Adjustment instructions<br />
The activation of the measuring system as safety-relevant subsystem is only possible via PC<br />
adjustment programs. Not all safety-relevant parameters can be adjusted with the adjustment<br />
module MINICOM. The set parameters must be checked and protected against unauthorised<br />
access (password, screwed housing cover, …).<br />
General instructions, see operating instructions manual<br />
Parameter settings<br />
The following software versions are required:<br />
- Sensor software: from 4.50.00<br />
- DTM-Collection: from 10/2003<br />
With the adjustment program PACTware, the SIL parameter settings must be activated in the<br />
Device Type Manager (DTM).<br />
Note<br />
If a reset is triggered on the sensor after the SIL parameters are set or if the failure mode =<br />
22 mA is changed, the sensor will loose its SIL qualification.<br />
3.3 Configuration of the processing unit<br />
If the measuring system delivers output currents > 21 mA or < 3.6 mA, it must be assumed<br />
that a failure has occurred.<br />
The processing unit must therefore interpret such current values as a failure and trigger a<br />
suitable fault signal.<br />