03.01.2014 Views

NetSure ITM Installation Manual - Gruber Power

NetSure ITM Installation Manual - Gruber Power

NetSure ITM Installation Manual - Gruber Power

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Positioning the DC UPS System<br />

3.0 POSITIONING THE DC UPS SYSTEM<br />

This section describes the environmental and mechanical considerations that must be taken into<br />

account when planning the positioning and cabling of the DC UPS system. This section also provides<br />

procedures for physical installation of the DC UPS cabinet.<br />

Because every site is unique, some subsections present a guide to general procedures and practices<br />

that should be observed by the installing engineer, rather than step-by-step installation instructions.<br />

3.1 General Requirements<br />

• The installer should be familiar with the installation requirements and techniques to be used in<br />

securing the DC UPS module (cabinet) to the floor. It is up to the customer to determine the<br />

requirements for anchoring the cabinet to the specific type of floor at the site, select proper<br />

anchors, and to investigate the proper use of the anchor.<br />

• This product is intended only for installation in a Restricted Access Location on or above a noncombustible<br />

surface.<br />

• Front and rear access is required for installation and operation (see Clearances in this section).<br />

3.2 General Guidelines for Positioning the DC UPS Modules<br />

Choose a location for the DC UPS system that offers:<br />

• Easy connection to inputs, outputs, and alarms.<br />

• Air circulation sufficient to expel heat produced by the DC UPS system.<br />

• Protection against moisture and excessive humidity.<br />

• Protection against dust and other particulate matter.<br />

• Enough space to service the DC UPS system (see Clearances in this section).<br />

• Compliance with fire prevention regulations and practices.<br />

3.2.1 Cable Entry<br />

DC distribution and alarm cables enter the DC UPS module from the top or bottom, depending on<br />

module configuration (top distribution feed or bottom distribution feed).<br />

AC input cables can enter either at the top or bottom. Conduit openings are provided in both locations.<br />

3.2.2 Environmental Considerations<br />

Before installing the DC UPS system, verify that the room satisfies the environmental conditions<br />

stipulated in 7.2 - Environmental, paying particular attention to the ambient temperature and air<br />

exchange system. Also refer to 7.2 - Environmental for details on heat dissipation.<br />

The DC UPS system should be installed in a cool, dry, clean-air environment with adequate ventilation<br />

to keep the ambient temperature within the specified operating range +23°F to +95°F (-5°C to<br />

+35°C).<br />

• Batteries are installed in the DC UPS module’s battery compartment. Temperature is a major factor<br />

in determining battery life and capacity. Battery manufacturers recommend an operating<br />

temperature of 77°F (25°C). Ambient temperatures higher than this reduce battery life; temperatures<br />

lower than this reduce battery capacity. For optimal battery performance and service life,<br />

inlet air temperature to the battery compartment (from the front of the system) should be maintained<br />

between +68°F to +77°F (+20°C to +25°C).<br />

The DC UPS module is cooled by internal fans. Cooling air enters the system through the front of the<br />

unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or<br />

cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit<br />

must be a minimum of 8 in. (203mm).<br />

13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!