Electrical Connections<br />

Figure 13 AC Input <strong>Power</strong> Connection Routing Options<br />

DC UPS MODULE WITH<br />

TOP FEED DC DISTRIBUTION<br />

AC enters at top.<br />

DC UPS MODULE WITH<br />

BOTTOM FEED DC DISTRIBUTION<br />

AC enters at top.<br />

Battery Compartment<br />

65kAic<br />

Circuit<br />

Breaker<br />

Run AC Cables<br />

from Top OR Bottom<br />

Battery Compartment<br />

65kAic<br />

Circuit<br />

Breaker<br />

Run AC Cables<br />

from Top OR Bottom<br />

AC enters at bottom.<br />

AC enters at bottom.<br />

Figure 14 Installing Conduit Fittings when AC is Fed from the Top<br />

1) Remove cover plate.<br />

Note: Cut cover plate in half if<br />

only one conduit being installed.<br />

2) Install one or two customer provided<br />

conduit fittings to supplied conduit plate.<br />

Customer provided<br />

conduit fittings.<br />

3) Secure conduit plate with conduit<br />

fittings installed to top of cabinet.<br />

Note: If only one conduit being installed,<br />

re-install plate that was cut in half.<br />

Figure 15 AC Input <strong>Power</strong> Connections<br />

DC UPS MODULE WITH<br />

BOTTOM FEED DC DISTRIBUTION<br />

DC UPS MODULE WITH<br />

TOP FEED DC DISTRIBUTION<br />

GND<br />

Stud<br />

factory wiring<br />

L1 L2 L3 L1 L2 L3<br />

AC IN A AC IN B<br />

A<br />

Feed<br />

GND<br />

Stud<br />

B (optional)<br />

Feed<br />

AC INPUT<br />

380/480VAC, 3 Phase, 50/60Hz<br />

AC INPUT<br />

380/480VAC, 3 Phase, 50/60Hz<br />

GND<br />

Stud<br />

A<br />

Feed<br />

AC IN A<br />

L1 L2 L3<br />

factory wiring<br />

B<br />

Feed (optional)<br />

AC IN B<br />

L1 L2 L3<br />

GND<br />

Stud<br />

One or two AC input circuit breakers are provided (depending on module configuration).<br />

Two ground studs (5/16” [M8]) are provided attached to the sides of the enclosure surrounding the AC input circuit breaker(s).<br />

Recommended torque is 124 in-lbs (14 Nm) for AC input circuit breaker connection.<br />

Recommended torque is 204-221 in-lbs (23-25 Nm) to grounding studs.<br />