Electrical Connections<br />
Figure 13 AC Input <strong>Power</strong> Connection Routing Options<br />
DC UPS MODULE WITH<br />
TOP FEED DC DISTRIBUTION<br />
AC enters at top.<br />
DC UPS MODULE WITH<br />
BOTTOM FEED DC DISTRIBUTION<br />
AC enters at top.<br />
Battery Compartment<br />
65kAic<br />
Circuit<br />
Breaker<br />
Run AC Cables<br />
from Top OR Bottom<br />
Battery Compartment<br />
65kAic<br />
Circuit<br />
Breaker<br />
Run AC Cables<br />
from Top OR Bottom<br />
AC enters at bottom.<br />
AC enters at bottom.<br />
Figure 14 Installing Conduit Fittings when AC is Fed from the Top<br />
1) Remove cover plate.<br />
Note: Cut cover plate in half if<br />
only one conduit being installed.<br />
2) Install one or two customer provided<br />
conduit fittings to supplied conduit plate.<br />
Customer provided<br />
conduit fittings.<br />
3) Secure conduit plate with conduit<br />
fittings installed to top of cabinet.<br />
Note: If only one conduit being installed,<br />
re-install plate that was cut in half.<br />
Figure 15 AC Input <strong>Power</strong> Connections<br />
DC UPS MODULE WITH<br />
BOTTOM FEED DC DISTRIBUTION<br />
DC UPS MODULE WITH<br />
TOP FEED DC DISTRIBUTION<br />
GND<br />
Stud<br />
factory wiring<br />
L1 L2 L3 L1 L2 L3<br />
AC IN A AC IN B<br />
A<br />
Feed<br />
GND<br />
Stud<br />
B (optional)<br />
Feed<br />
AC INPUT<br />
380/480VAC, 3 Phase, 50/60Hz<br />
AC INPUT<br />
380/480VAC, 3 Phase, 50/60Hz<br />
GND<br />
Stud<br />
A<br />
Feed<br />
AC IN A<br />
L1 L2 L3<br />
factory wiring<br />
B<br />
Feed (optional)<br />
AC IN B<br />
L1 L2 L3<br />
GND<br />
Stud<br />
One or two AC input circuit breakers are provided (depending on module configuration).<br />
Two ground studs (5/16” [M8]) are provided attached to the sides of the enclosure surrounding the AC input circuit breaker(s).<br />
Recommended torque is 124 in-lbs (14 Nm) for AC input circuit breaker connection.<br />
Recommended torque is 204-221 in-lbs (23-25 Nm) to grounding studs.<br />
25