Electrical Connections<br />
Table 3<br />
Programmable Digital Inputs<br />
Programmable<br />
Digital Input<br />
Pin No.<br />
Dedicated to...<br />
Customer<br />
Custom Digital Input<br />
1<br />
J3-1 –<br />
J3-2 +<br />
Available for Customer<br />
Custom Digital Input<br />
2<br />
J3-3 –<br />
J3-4 +<br />
Available for Customer<br />
Custom Digital Input<br />
3<br />
J3-5 –<br />
J3-6 +<br />
Available for Customer<br />
Custom Digital Input<br />
4<br />
J4-1 –<br />
J4-2 +<br />
PCU EPO<br />
factory wired<br />
5<br />
J4-3 –<br />
J4-4 +<br />
Fan Supply Alarm<br />
factory wired<br />
6<br />
J4-5 –<br />
J4-6 +<br />
Fan Alarm<br />
factory wired<br />
7<br />
J5-1 –<br />
J5-2 +<br />
Available for Customer<br />
Custom Digital Input<br />
8<br />
J5-3 –<br />
J5-4 +<br />
Available for Customer<br />
Custom Digital Input<br />
--<br />
J5-5<br />
J5-6<br />
--<br />
Relay Output Connections<br />
The IB2 board provides eight (8) programmable alarm relays with Form-C contacts. Default relay<br />
assignments are documented in Table 4. A blank column in Table 4 is also provided if you want to<br />
document a custom configuration. Alarm relay contacts are rated for 2A @ 30VDC and 0.5A @<br />
125VAC (60W maximum power consumption).<br />
• Each relay can be individually configured to activate for any system alarm condition.<br />
• Refer to DC UPS User <strong>Manual</strong> for programming instructions.<br />
27