Electrical Connections<br />

Table 3<br />

Programmable Digital Inputs<br />

Programmable<br />

Digital Input<br />

Pin No.<br />

Dedicated to...<br />

Customer<br />

Custom Digital Input<br />

1<br />

J3-1 –<br />

J3-2 +<br />

Available for Customer<br />

Custom Digital Input<br />

2<br />

J3-3 –<br />

J3-4 +<br />

Available for Customer<br />

Custom Digital Input<br />

3<br />

J3-5 –<br />

J3-6 +<br />

Available for Customer<br />

Custom Digital Input<br />

4<br />

J4-1 –<br />

J4-2 +<br />

PCU EPO<br />

factory wired<br />

5<br />

J4-3 –<br />

J4-4 +<br />

Fan Supply Alarm<br />

factory wired<br />

6<br />

J4-5 –<br />

J4-6 +<br />

Fan Alarm<br />

factory wired<br />

7<br />

J5-1 –<br />

J5-2 +<br />

Available for Customer<br />

Custom Digital Input<br />

8<br />

J5-3 –<br />

J5-4 +<br />

Available for Customer<br />

Custom Digital Input<br />

--<br />

J5-5<br />

J5-6<br />

--<br />

Relay Output Connections<br />

The IB2 board provides eight (8) programmable alarm relays with Form-C contacts. Default relay<br />

assignments are documented in Table 4. A blank column in Table 4 is also provided if you want to<br />

document a custom configuration. Alarm relay contacts are rated for 2A @ 30VDC and 0.5A @<br />

125VAC (60W maximum power consumption).<br />

• Each relay can be individually configured to activate for any system alarm condition.<br />

• Refer to DC UPS User <strong>Manual</strong> for programming instructions.<br />

27