Configuring the <strong>Case</strong> <strong><strong>Control</strong>ler</strong> From MT Alliance<br />
Installing the <strong>Case</strong> <strong><strong>Control</strong>ler</strong><br />
Config Tab<br />
The Config tab provides detailed settings for how the <strong>Case</strong> <strong><strong>Control</strong>ler</strong><br />
is being used. Many of these settings impact other parameters and setpoints<br />
later in the configuration process.<br />
If any changes are made, all settings on Inputs / Outputs tab and<br />
<strong>Control</strong> tab must verified.<br />
Process <strong>Control</strong> Type<br />
Specify the control scheme desired:<br />
Temperature <strong>Control</strong> with Superheat Limit controls the expansion<br />
valve to optimize case temperature, as long as the superheat is at<br />
an acceptable level. If superheat falls to the specified threshold,<br />
the controller will begin closing the valve. Once superheat returns<br />
above the threshold, the controller will resume maintaining case<br />
temperature.<br />
Superheat <strong>Control</strong> Only controls the expansion valve to maintain the<br />
specified superheat.<br />
Temperature <strong>Control</strong> Only controls the expansion valve to maintain<br />
a specified case temperature.<br />
End Defrost Source<br />
Specify the temperature input that will trigger the controller to end<br />
defrost. By default, the controller uses the dedicated defrost termination<br />
sensor.<br />
14