Configuring the <strong>Case</strong> <strong><strong>Control</strong>ler</strong> From MT Alliance<br />

Installing the <strong>Case</strong> <strong><strong>Control</strong>ler</strong><br />

Config Tab<br />

The Config tab provides detailed settings for how the <strong>Case</strong> <strong><strong>Control</strong>ler</strong><br />

is being used. Many of these settings impact other parameters and setpoints<br />

later in the configuration process.<br />

If any changes are made, all settings on Inputs / Outputs tab and<br />

<strong>Control</strong> tab must verified.<br />

Process <strong>Control</strong> Type<br />

Specify the control scheme desired:<br />

Temperature <strong>Control</strong> with Superheat Limit controls the expansion<br />

valve to optimize case temperature, as long as the superheat is at<br />

an acceptable level. If superheat falls to the specified threshold,<br />

the controller will begin closing the valve. Once superheat returns<br />

above the threshold, the controller will resume maintaining case<br />

temperature.<br />

Superheat <strong>Control</strong> Only controls the expansion valve to maintain the<br />

specified superheat.<br />

Temperature <strong>Control</strong> Only controls the expansion valve to maintain<br />

a specified case temperature.<br />

End Defrost Source<br />

Specify the temperature input that will trigger the controller to end<br />

defrost. By default, the controller uses the dedicated defrost termination<br />

sensor.<br />