Case Controller Supermarket Control Solutions - Sporlan Online
Case Controller Supermarket Control Solutions - Sporlan Online
Case Controller Supermarket Control Solutions - Sporlan Online
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
7<br />
A:<br />
Wiring Diagram / Dimensions<br />
Appendices<br />
12.50” / 318 mm<br />
11.90” / 302 mm<br />
0.48”<br />
12 mm<br />
2.47”<br />
63 mm<br />
F2<br />
F3<br />
F4<br />
4.56”<br />
116 mm<br />
F1<br />
120/240V Power<br />
L N Earth<br />
FAN ELEC. DEFROST LIGHTING<br />
COM<br />
NO COM NC NO COM NC<br />
NO NC<br />
NETWORK RS485 DC OUT<br />
A B A B 26V Gnd<br />
P evap T evap T air T def T aux Di1 Di2 Antisw Valve<br />
5V S Gnd + - + - + - 2 3 1 4<br />
PWR<br />
PWR<br />
PWR<br />
0.40”<br />
10 mm<br />
120/240V<br />
Power<br />
Fan<br />
Front View<br />
(ABS Plastic Enclosure)<br />
Electric Defrost<br />
Lighting<br />
Network<br />
Pressure Transducer<br />
P/N 023-0076 (Blue)<br />
Temperature Sensor (T° COIL)<br />
NET<br />
RED<br />
WHITE<br />
BLACK<br />
SHIELD<br />
Switch<br />
BLACK<br />
WHITE<br />
GREEN<br />
RED<br />
SER or SEI<br />
Typical<br />
Stepper<br />
Motor Valve<br />
P/N 023-0072 (Orange)<br />
Temperature Sensor (T° DEF)<br />
P/N 023-0073 (Green)<br />
Temperature Sensor (T° AIR)<br />
2.15” / 55 mm<br />
Side View<br />
IN / OUT Description<br />
POWER: 120V or 240VAC, field installed by electrical contractor<br />
FAN: Maximum 4Amp when driven directly by the controller - need an<br />
external interface relay/contractor when amperage > 4Amp<br />
ELEC. DEFROST: Always use an external interface relay or contactor<br />
LIGHTING: Maximum 4Amp when driven directly by the controller - need an<br />
external interface relay/contactor when amperage > 4Amp<br />
NETWORK: Echelon Type 2#18, Stranded, 7/26 UTP (Unshielded Twisted<br />
Pair) Belden 8461 type or equivalent, field installed by the EMS<br />
Contractor<br />
RS485/DC OUT: For future use<br />
Pevap: Pressure transducer used with T° COIL to calculate Superheat<br />
Tevap: 10K T° sensor P/N 023-0076 used for Superheat (blue)<br />
Tair: 10K T° sensor P/N 023-0073 used for alarm monitoring (green)<br />
Tdef: 10K T° sensor P/N 023-0072 used for end defrost (orange)<br />
Taux: Auxiliary T° sensor 10K for Temperature monitoring or end defrost<br />
located in return air<br />
Di1/Di2: Configurable switches for following applications: Clean switch, Door<br />
Ajar & Dual Temperature <strong>Case</strong>. Type of switch: software, remote or local<br />
Antisw: Pulse output to control external solid state relay for anti-sweat heater<br />
(SSR supplied by case manufacturer)<br />
Valve: Stepper motor EEV<br />