7<br />

A:<br />

Wiring Diagram / Dimensions<br />

Appendices<br />

12.50” / 318 mm<br />

11.90” / 302 mm<br />

0.48”<br />

12 mm<br />

2.47”<br />

63 mm<br />

F2<br />

F3<br />

F4<br />

4.56”<br />

116 mm<br />

F1<br />

120/240V Power<br />

L N Earth<br />

FAN ELEC. DEFROST LIGHTING<br />

COM<br />

NO COM NC NO COM NC<br />

NO NC<br />

NETWORK RS485 DC OUT<br />

A B A B 26V Gnd<br />

P evap T evap T air T def T aux Di1 Di2 Antisw Valve<br />

5V S Gnd + - + - + - 2 3 1 4<br />

PWR<br />

PWR<br />

PWR<br />

0.40”<br />

10 mm<br />

120/240V<br />

Power<br />

Fan<br />

Front View<br />

(ABS Plastic Enclosure)<br />

Electric Defrost<br />

Lighting<br />

Network<br />

Pressure Transducer<br />

P/N 023-0076 (Blue)<br />

Temperature Sensor (T° COIL)<br />

NET<br />

RED<br />

WHITE<br />

BLACK<br />

SHIELD<br />

Switch<br />

BLACK<br />

WHITE<br />

GREEN<br />

RED<br />

SER or SEI<br />

Typical<br />

Stepper<br />

Motor Valve<br />

P/N 023-0072 (Orange)<br />

Temperature Sensor (T° DEF)<br />

P/N 023-0073 (Green)<br />

Temperature Sensor (T° AIR)<br />

2.15” / 55 mm<br />

Side View<br />

IN / OUT Description<br />

POWER: 120V or 240VAC, field installed by electrical contractor<br />

FAN: Maximum 4Amp when driven directly by the controller - need an<br />

external interface relay/contractor when amperage > 4Amp<br />

ELEC. DEFROST: Always use an external interface relay or contactor<br />

LIGHTING: Maximum 4Amp when driven directly by the controller - need an<br />

external interface relay/contactor when amperage > 4Amp<br />

NETWORK: Echelon Type 2#18, Stranded, 7/26 UTP (Unshielded Twisted<br />

Pair) Belden 8461 type or equivalent, field installed by the EMS<br />

Contractor<br />

RS485/DC OUT: For future use<br />

Pevap: Pressure transducer used with T° COIL to calculate Superheat<br />

Tevap: 10K T° sensor P/N 023-0076 used for Superheat (blue)<br />

Tair: 10K T° sensor P/N 023-0073 used for alarm monitoring (green)<br />

Tdef: 10K T° sensor P/N 023-0072 used for end defrost (orange)<br />

Taux: Auxiliary T° sensor 10K for Temperature monitoring or end defrost<br />

located in return air<br />

Di1/Di2: Configurable switches for following applications: Clean switch, Door<br />

Ajar & Dual Temperature <strong>Case</strong>. Type of switch: software, remote or local<br />

Antisw: Pulse output to control external solid state relay for anti-sweat heater<br />

(SSR supplied by case manufacturer)<br />

Valve: Stepper motor EEV<br />