<strong>INTERFACE</strong> <strong>Cabling</strong><br />

VARIOFACE wiring interface<br />

Miniature relay REL-MR<br />

The robust relays are used as interface<br />

relays throughout process <strong>and</strong> production<br />

engineering.<br />

The main features of these relays are their<br />

compact design, reliable electrical isolation,<br />

<strong>and</strong> compliance with the most important<br />

st<strong>and</strong>ards, as well as the number of variants.<br />

Note:<br />

For diagrams of operating voltage ranges,<br />

refer to page 176.<br />

Note:<br />

If the specified maximum values for multi-layer contact relays are<br />

exceeded, the gold plating is destroyed. The maximum values of the<br />

power contact relay are then valid. This can result in a shorter<br />

service life than with a pure power contact.<br />

REL-MR-G24/1<br />

Plug-in miniature relay<br />

1 N/O contact (1)<br />

Width 5<br />

A1 12<br />

P<br />

A2 11<br />

Description<br />

Plug-in miniature relay, with power contact<br />

Input voltage<br />

U N<br />

Type Order No.<br />

Pcs. /<br />

Pkt.<br />

1 12 V DC<br />

2 24 V DC REL-MR-G 24/1 2961037 8<br />

3 48 V DC<br />

4 60 V DC<br />

With power contact 5 110 V DC<br />

6 230 V AC<br />

Plug-in miniature relay, with multi-layer contact<br />

1 12 V DC<br />

2 24 V DC<br />

3 48 V DC<br />

4 60 V DC<br />

With gold contact 5 110 V DC<br />

6 230 V AC<br />

Technical data 1<br />

Input data<br />

Permissible range (based on U N ) -<br />

Permissible range (based on U N ) 0.8 -<br />

1.1<br />

Typ. input current at U N [mA] 5<br />

Typ. response time at U N [ms] 5<br />

Typ. response time at U N ( depending on phase relation )<br />

[ms]<br />

Typ. release time at U N [ms] 2<br />

Typ. release time at U N ( depending on phase relation )<br />

[ms]<br />

Output data<br />

<strong>Contact</strong> type<br />

Double contact, 1 N/O contact<br />

<strong>Contact</strong> material<br />

AgNi 90/10, + 5 µm hard gold-plated<br />

Max. switching voltage<br />

250 V AC / 125 V DC<br />

Min. switching voltage<br />

5 V DC<br />

Limiting continuous current<br />

3 A<br />

Max. inrush current<br />

5 A<br />

Max. interrupting rating, ohmic load<br />

250 V AC -<br />

General data<br />

Test voltage (winding / contact)<br />

2 kV AC (50 Hz, 1 min)<br />

Test voltage (contact/contact) -<br />

Ambient temperature range -40°C ... 85°C<br />

Rated operating mode<br />

100% operating factor<br />

Mechanical service life<br />

Approx. 2 x 10 7 cycles<br />

St<strong>and</strong>ards/regulations<br />

DIN VDE 0110, IEC 255/DIN VDE 0435 (in relevant parts)<br />

Assembly position/mounting<br />

Any<br />

Dimensions W / H / D 5 mm / 17 mm / 23 mm<br />

304 PHOENIX CONTACT<br />

Courtesy of <strong>Power</strong>/<strong>mation</strong>. 1310 Energy Lane, Saint Paul, MN 55108<br />

info@power<strong>mation</strong>.com - 800-843-9859 - www.power<strong>mation</strong>.com