12.05.2014 Views

Automating Manufacturing Systems - Process Control and ...

Automating Manufacturing Systems - Process Control and ...

Automating Manufacturing Systems - Process Control and ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

plc timers - 9.10<br />

A<br />

TOF<br />

Timer T4:0<br />

Time Base 0.01<br />

Preset 350<br />

Accum. 0<br />

(DN)<br />

(EN)<br />

A<br />

T4:0 EN<br />

T4:0/DN<br />

T4:0/TT<br />

T4:0.Accum.<br />

0<br />

3<br />

3.5<br />

0 3 6 9.5 10 16 18 20<br />

Figure 9.10<br />

An Allen Bradley Off-Delay Timer<br />

Retentive off-delay (RTF) timers have few applications <strong>and</strong> are rarely used, therefore<br />

many PLC vendors do not include them.<br />

An example program is shown in Figure 9.11. In total there are four timers used in<br />

this example, T4:1 to T4:4. The timer instructions are shown with a shorth<strong>and</strong> notation<br />

with the timebase <strong>and</strong> preset values combined as the delay. All four different types of<br />

counters have the input I/1. Output O/1 will turn on when the TON counter T4:1 is done.<br />

All four of the timers can be reset with input I/2.