plc timers - 9.14<br />

T4:1/DN<br />

T4:0/DN<br />

T4:1/TT<br />

TON<br />

Timer T4:0<br />

Delay 0.5s<br />

TON<br />

Timer T4:1<br />

Delay 0.5s<br />

Light<br />

Figure 9.14<br />

Another Timer Example<br />

9.4 COUNTERS<br />

There are two basic counter types: count-up <strong>and</strong> count-down. When the input to a<br />

count-up counter goes true the accumulator value will increase by 1 (no matter how long<br />

the input is true.) If the accumulator value reaches the preset value the counter DN bit will<br />

be set. A count-down counter will decrease the accumulator value until the preset value is<br />

reached.<br />

An Allen Bradley count-up (CTU) instruction is shown in Figure 9.15. The<br />

instruction requires memory in the PLC to store values <strong>and</strong> status, in this case is C5:0.The<br />

C5: indicates that it is counter memory, <strong>and</strong> the 0 indicates that it is the first location. The<br />

preset value is 4 <strong>and</strong> the value in the accumulator is 2. If the input A were to go from false<br />

to true the value in the accumulator would increase to 3. If A were to go off, then on again<br />

the accumulator value would increase to 4, <strong>and</strong> the DN bit would go on. The count can<br />

continue above the preset value. If input B goes true the value in the counter accumulator<br />

will become zero.