12.05.2014 Views

Automating Manufacturing Systems - Process Control and ...

Automating Manufacturing Systems - Process Control and ...

Automating Manufacturing Systems - Process Control and ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

plc function ref - 34.10<br />

RTO - RetentiveTimer On<br />

A<br />

Description:<br />

Status Bits:<br />

Registers:<br />

RTO<br />

RETENTIVE TIMER ON<br />

Timer T4:0<br />

Time Base 1.0<br />

Preset 10<br />

Accum. 0<br />

This timer will delay turning on. When the input turns on the accumulated<br />

value (ACC) will start to increase from zero. When the preset (PRE)<br />

value is reached the DN bit is set. If the input goes false the accumulator<br />

value is not reset to zero. To reset the timer <strong>and</strong> turn off the timer the<br />

RES instruction should be used.<br />

EN<br />

TT<br />

DN<br />

ACC<br />

PRE<br />

Available on: Micrologix, PLC-5<br />

This bit is true while the input to the timer is true<br />

This bit is true while the accumulator value is increasing<br />

This bit is true when the accumulator value is less than the preset<br />

value<br />

The time that has passed since the input went true<br />

The maximum time delay before the timer goes on<br />

34.1.4 Compare<br />

CMP - CoMPare<br />

CMP<br />

COMPARE<br />

Expression<br />

“(N7:0 + 8) > N7:1”<br />

A<br />

Description:<br />

Status Bits:<br />

This function uses a free form expression to compare the two values. The<br />

comparison values that are allowed include =, >, >=, ,