continuous sensors - 23.32<br />

23.2.9 Others<br />

A number of other detectors/sensors are listed below,<br />

Combustion - gases such as CO2 can be an indicator of combustion<br />

Humidity - normally in gases<br />

Dew Point - to determine when condensation will form<br />

23.3 INPUT ISSUES<br />

Signals from sensors are often not in a form that can be directly input to a controller.<br />

In these cases it may be necessary to buy or build signal conditioners. Normally, a signal<br />

conditioner is an amplifier, but it may also include noise filters, <strong>and</strong> circuitry to<br />

convert from current to voltage. This section will discuss the electrical <strong>and</strong> electronic<br />

interfaces between sensors <strong>and</strong> controllers.<br />

Analog signal are prone to electrical noise problems. This is often caused by electromagnetic<br />

fields on the factory floor inducing currents in exposed conductors. Some of<br />

the techniques for dealing with electrical noise include;<br />

twisted pairs - the wires are twisted to reduce the noise induced by magnetic fields.<br />

shielding - shielding is used to reduce the effects of electromagnetic interference.<br />

single/double ended inputs - shared or isolated reference voltages (commons).<br />

When a signal is transmitted through a wire, it must return along another path. If<br />

the wires have an area between them the magnetic flux enclosed in the loop can induce<br />

current flow <strong>and</strong> voltages. If the wires are twisted, a few times per inch, then the amount<br />

of noise induced is reduced. This technique is common in signal wires <strong>and</strong> network cables.<br />

A shielded cable has a metal sheath, as shown in Figure 23.32. This sheath needs<br />

to be connected to the measuring device to allow induced currents to be passed to ground.<br />

This prevents electromagnetic waves to induce voltages in the signal wires.