plc function ref - 34.9<br />

TON - Timer ON<br />

A<br />

Description:<br />

Status Bits:<br />

Registers:<br />

TON<br />

TIMER ON DELAY<br />

Timer T4:0<br />

Time Base 1.0<br />

Preset 10<br />

Accum. 0<br />

This timer will delay turning on, but will turn off immediately. Once the<br />

input turns on the accumulated value (ACC) will start to increase from<br />

zero. When the preset (PRE) value is reached the DN bit is set. The done<br />

bit will turn off <strong>and</strong> the accumulator will reset to zero if the input goes<br />

false.<br />

EN<br />

TT<br />

DN<br />

ACC<br />

PRE<br />

Available on: Micrologix, PLC-5<br />

This bit is true while the input to the timer is true<br />

This bit is true while the accumulator value is increasing<br />

This bit is true when the accumulator value is equal to the preset<br />

value<br />

The time that has passed since the input went true<br />

The maximum time delay before the timer goes on