Although it is common practice to install a larger fuse during<br />

service diagnosis, you should not leave a larger fuse in<br />

the unit when you leave the site. This could cause a serious<br />

unit failure.<br />

3. MISWIRING<br />

Is gear motor wired correctly and wire connections tight.<br />

Check the wiring diagram for the proper wiring.<br />

4. BIN CONTROL SWITCH DOES NOT OPERATE<br />

Check the bin control operation. A bad or miswired bin<br />

control can cause ice to back up in the spout and chute and<br />

cause higher gear motor amperage. Is Bin Control wired<br />

correctly and are the wire connections tight.<br />

Make sure there are no metallic components interfering<br />

with the magnetic bin control. Verify top panel is non-magnetic.<br />

Assure that the proximity switch is mount properly.<br />

The switch must be secure and mounted level to the chute<br />

top. Does the Bin Control Paddle move freely and is it<br />

unobstructed?<br />

As you can see, there are many factors that can cause a<br />

gear motor to fail. A gear motor check list comes with a<br />

service replacement part. The check list can be used as a<br />

diagnostic tool. If the gear motor is under warranty, the<br />

checklist should be completed and submitted with the warranty<br />

claim.<br />

GEAR MOTOR STRESS<br />

When looking for the cause of a gear motor failure, you<br />

should consider anything that will add stress to the assembly.<br />

Stress on the gear motor will increase the gear motor<br />

amperage and torque. The most common causes for stress<br />

is scale on the auger surface and evaporator walls. Scale<br />

nsulates the evaporator walls and causes reduced heat<br />

transfer. As a result, the ice will be wet and mushy. This<br />

poor quality ice does not extrude well and tends to pack in<br />

the evaporator outlet.<br />

Heavy scale build up must be removed using an acid based<br />

cleaner which will loosen the scale. Follow the cleaning<br />

instructions provided on the cleaning label to preform a<br />

maintenance cleaning. If the unit has not been cleaned and<br />

maintained frequently, it may require you to pull the auger<br />