TECH - SPEC'S Technician's Pocket Guide - Hoshizaki America, Inc.
TECH - SPEC'S Technician's Pocket Guide - Hoshizaki America, Inc.
TECH - SPEC'S Technician's Pocket Guide - Hoshizaki America, Inc.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
not starting freeze cycle, check defrost<br />
completion timer adjustment, thermistor for open<br />
circuit, discharge line temperature, C efficiency,<br />
and if HGV is fully open.<br />
C) Freeze cycle – C remains energized, PM, (LV<br />
on RS model), and FM energize…WV & HGV<br />
de-energize. Unit is held in freeze by 5 minute<br />
short cycle protection timer. After 5 minutes<br />
freeze cycle operation to transferred to FS for<br />
freeze termination. During first 5 minutes of<br />
freeze, confirm that evaporator temperature<br />
drops. After 7 minutes in freeze, remove black<br />
FS lead from K5 connector…Unit should<br />
immediately switch to pump out cycle.<br />
Diagnosis: If evaporator is not cold, check for HGV<br />
still open, TXV not opening properly, WV<br />
continuing to fill reservoir, improper unit pres<br />
sures, and inoperative C. If unit remains in freeze<br />
with FS removed replace board. * Normal freeze<br />
cycle will last 20 ~ 40 minutes depending on<br />
model and conditions. Cycle times and<br />
pressures should follow performance data<br />
provided in Tech –Specs.<br />
D) Pump Out Cycle – (10/20 second pump out)<br />
C remains energized, HGV energizes, FM deenergizes,<br />
PM stops for 2 seconds and starts in<br />
reverse rotation for 10/20 seconds.( This<br />
removes contaminants from the water reservoir<br />
through check valve and down the drain and<br />
allows for power flush of FS.) Check clear<br />
tubing at check valve housing or unit drain for<br />
water flow.<br />
Diagnosis: If PM does not reverse, check PM circuit<br />
and capacitor. If water does not pump out,<br />
remove housing and check/clean valve<br />
assembly.<br />
E) Normal Harvest Cycle –same as Initial Harvest<br />
Cycle – Return to B)…* Unit continues to cycle<br />
through B)…C)…& D) (Setting can be adjusted<br />
to skip D until every 2, 5, of 10 cycles)…until bin<br />
control is satisfied or power is switched OFF.<br />
• Unit always restarts at A).<br />
Legend:<br />
C – Compressor CC – Contactor Coil FM – Condenser Fan Motor<br />
FS – Float Switch HGV – Hot Gas Valve LV – Line Valve<br />
PM – Pump Motor RS – Remote System WV – Inlet Water Valve<br />
36<br />