Pressure switch chart for R-404A models:<br />
Models part number cut out cut in<br />
(psig.) (psig.)<br />
DCM-240B 3A0740-01 400 ±10 270 ±10<br />
All KM & DCM water-cooled,<br />
All F models 433441-05 384 ± 21.3 284± 21.3<br />
DCM-500/750BAF All KM<br />
air & remote, 433441-07 412 ± 21. 327 ± 21.3<br />
BIN CONTROL<br />
KM BIN CONTROLS:<br />
KM/KML cubers will use one of three types of bin controls.<br />
The type of bin control will vary depending on the unit style,<br />
or model and serial number.<br />
1. THERMOSTATIC BIN CONTROL:<br />
The thermostatic bin control is the primary control that supplies<br />
115 volts to all major components in the unit except the<br />
compressor. When this control is closed, 115V is supplied<br />
to the control transformer and to the K1 control board<br />
connector which switches 115 volts to the components as<br />
the sequence dictates. A thermostatic capillary bulb is<br />
mounted in the ice drop zone area or on a drop down<br />
bracket which extends into the bin cavity.<br />
The Thermostatic control is normally closed. (It opens on<br />
temperature drop and closes on temperature rise.) When<br />
ice touches the thermostatic bulb, the bulb pressure opens<br />
the bin control switch to shut the unit down. The thermostatic<br />
bin control will shut the unit down at any point in the<br />
sequence of operation if ice contacts the control bulb. The<br />
shut down time will depend on the control adjustment. This<br />
adjustment is factory set however it should always be<br />
checked at start-up to assure proper operation. High<br />
altitude areas require adjustment. When ice is moved<br />
away from the bulb, the unit will always restart in the 1-<br />
minute fill cycle.<br />
Note: The unit will not operate in either ICE or WASH unless<br />
the thermostatic bin control switch is closed.<br />
Larger M models and S models include a drop down bulb<br />
bracket. This bracket should be secured to the unit base<br />
and the control plug connection must be made before<br />
the unit will operate. A bin control extension bracket is<br />
included with all S models. Be sure to install the extension<br />
28<br />