Pressure switch chart for R-404A models:<br />

Models part number cut out cut in<br />

(psig.) (psig.)<br />

DCM-240B 3A0740-01 400 ±10 270 ±10<br />

All KM & DCM water-cooled,<br />

All F models 433441-05 384 ± 21.3 284± 21.3<br />

DCM-500/750BAF All KM<br />

air & remote, 433441-07 412 ± 21. 327 ± 21.3<br />

BIN CONTROL<br />

KM BIN CONTROLS:<br />

KM/KML cubers will use one of three types of bin controls.<br />

The type of bin control will vary depending on the unit style,<br />

or model and serial number.<br />

1. THERMOSTATIC BIN CONTROL:<br />

The thermostatic bin control is the primary control that supplies<br />

115 volts to all major components in the unit except the<br />

compressor. When this control is closed, 115V is supplied<br />

to the control transformer and to the K1 control board<br />

connector which switches 115 volts to the components as<br />

the sequence dictates. A thermostatic capillary bulb is<br />

mounted in the ice drop zone area or on a drop down<br />

bracket which extends into the bin cavity.<br />

The Thermostatic control is normally closed. (It opens on<br />

temperature drop and closes on temperature rise.) When<br />

ice touches the thermostatic bulb, the bulb pressure opens<br />

the bin control switch to shut the unit down. The thermostatic<br />

bin control will shut the unit down at any point in the<br />

sequence of operation if ice contacts the control bulb. The<br />

shut down time will depend on the control adjustment. This<br />

adjustment is factory set however it should always be<br />

checked at start-up to assure proper operation. High<br />

altitude areas require adjustment. When ice is moved<br />

away from the bulb, the unit will always restart in the 1-<br />

minute fill cycle.<br />

Note: The unit will not operate in either ICE or WASH unless<br />

the thermostatic bin control switch is closed.<br />

Larger M models and S models include a drop down bulb<br />

bracket. This bracket should be secured to the unit base<br />

and the control plug connection must be made before<br />

the unit will operate. A bin control extension bracket is<br />

included with all S models. Be sure to install the extension<br />

28<br />