Energy Consumption Figures:<br />

• Actual total annual energy consumption was 60% higher than<br />

expected. With an overall figure <strong>of</strong> 144kWh/m2 in 1998 falling to<br />

135kWh/m2 in 1999, compared with target <strong>of</strong> 83 kWh/m2.<br />

In 1999, electricity: 48 kWh/m2 (target 36 kWh/m2)<br />

gas: 87 kWh/m2 (target 47 kWh/m2)<br />

• High <strong>of</strong>fice electricity load is largely due to a high-performance<br />

computer suite in <strong>the</strong> ground floor, operating continuously.<br />

• Main increase caused by space heating requirements, brought about<br />

in part by building envelope integrity. Air leakage was measured as<br />

being 60% greater than <strong>the</strong> target air leakage index <strong>of</strong> 7.5m3/hr per<br />

m2 in <strong>the</strong> <strong>of</strong>fices & almost twice <strong>the</strong> target value in <strong>the</strong> rest <strong>of</strong> <strong>the</strong><br />

building. This has lead to <strong>the</strong> commissioning <strong>of</strong> a full air leakage<br />

audit with proposed remedial measures.<br />

3.2 The Commerzbank Headquarters, Frankfurt, Germany<br />

Architects: Foster and Partners, London<br />

• World’s first ecological tower: challenges conventional sealed box; 60<br />

stories high<br />

• Winter gardens spiral up <strong>the</strong> tower to be visual focus for four-storey<br />

clusters <strong>of</strong> <strong>of</strong>fices, linked to a central atrium, running full-height<br />

through building and acting as a ventilation chimney<br />

• Triangular plan: lifts and stairs located at corners to free up <strong>the</strong> core;<br />

16.5m floor slabs<br />

• Brings outside into <strong>the</strong> plan; maximizing daylighting; provides views<br />

across city<br />

• External temp reaches 35 degrees C. Aim to naturally ventilate for<br />

65% <strong>of</strong> year<br />

Lecture: Intelligent buildings, <strong>of</strong>fices 79