VAV Controller<br />
www.prolon.net<br />
• Cooling Integral: Defines the amount of time required for the cooling integral<br />
component of the demand to equalize the proportional component. Setting this value<br />
to zero removes the cooling integral component of the demand.<br />
Units MIN MAX Default<br />
Minutes 0 120 15<br />
• Heating Integral: Defines the amount of time required for the heating integral<br />
component of the demand to equalize the proportional component. Setting this value<br />
to zero removes the heating integral component of the demand<br />
Units MIN MAX Default<br />
Minutes 0 120 15<br />
2.1.3.2 Setpoints<br />
• Default Heating Setpoint: When there is no exterior source (thermostat) supplying the<br />
VAV Controller with a heating setpoint, this is the value used as the heating setpoint.<br />
Units MIN MAX Default<br />
°C 5 30 21.5<br />
°F 41 86 70.7<br />
• Occupied Deadband: The deadband between the occupied heating setpoint and the<br />
occupied cooling setpoint.<br />
Units MIN MAX Default<br />
°C 0.5 15 1<br />
°F 0.9 27 1.8<br />
• Setpoints Limits: These are the minimum and maximum values of the setpoints. These<br />
values overwrite any input to the VAV Controller that is beyond their boundaries.<br />
Used during occupied mode ONLY.<br />
• Minimum Heating Setpoint<br />
Units MIN MAX Default<br />
°C 5 30 19<br />
°F 41 86 66.2<br />
• Maximum Heating Setpoint<br />
Units MIN MAX Default<br />
°C 6 44.5 25<br />
°F 42.8 112.1 77<br />
• Minimum Cooling Setpoints<br />
Units MIN MAX Default<br />
°C 5.5 44 20<br />
°F 41.9 111.2 68<br />
• Maximum Cooling Setpoints<br />
Units MIN MAX Default<br />
°C 6.5 45 26<br />
°F 43.7 113 78.8<br />