VC1000 Focus Guide - ProLon
VC1000 Focus Guide - ProLon
VC1000 Focus Guide - ProLon
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
VAV Controller<br />
www.prolon.net<br />
• Math 1-5: The output is calculated using the chosen math function. In a<br />
standard <strong>ProLon</strong> Modbus network, the VAV Controller will use the math<br />
functions provided by the network master. In Lon or BACnet, setting an output<br />
to use math functions will automatically activate the VAV Controller’s own math<br />
calculations (even if this was not enabled in the Math Functions configuration<br />
screen). See the Math Functions configuration screen on p.33 for more details.<br />
• Off: The output remains inactive and will not appear on the Home screen.<br />
2.1.5.1 Setpoint Selection*<br />
• Heating Setpoint: The desired setpoint in heating mode. Setpoint cannot be zero.<br />
• Cooling Setpoint: The desired setpoint in cooling mode. Setpoint cannot be zero.<br />
2.1.5.2 Control Mode Selection*<br />
• Proportional Band: In proportional band control, the output is zero when the demand<br />
reaches the setpoint, increases proportionally with the demand by pulsing (Outputs 1<br />
to 4) or modulating (Output 5), and finally reaches 100% when the demand reaches<br />
the setpoint + proportional band (see figure below). The sum of the setpoint and the<br />
demand cannot be greater than 100%.<br />
Proportional Band<br />
0%<br />
Output = 0% Output = 100%<br />
Demand<br />
Setpoint<br />
Figure 2.1.12: Proportion deadband diagram<br />
Ex.: Setpoint = 25%<br />
Proportional band = 50%<br />
Demand = 45%<br />
Output = ((45-25)x100)/50 = 40%<br />
• Differential: In differential mode, the output alternates between 0 and 100% (ON/OFF).<br />
From an OFF state, the output becomes ON when the demand passes (setpoint +<br />
differential/2) and remains ON until the demand goes back down below (setpoint –<br />
differential/2) (see figure below). The setpoint must always be greater then the<br />
differential. The sum of the setpoint and the differential must be less than 100%.<br />
19<br />
www.prolon.net<br />
info@prolon.net