20.11.2014 Views

VC1000 Focus Guide - ProLon

VC1000 Focus Guide - ProLon

VC1000 Focus Guide - ProLon

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

VAV Controller<br />

www.prolon.net<br />

• Math 1-5: The output is calculated using the chosen math function. In a<br />

standard <strong>ProLon</strong> Modbus network, the VAV Controller will use the math<br />

functions provided by the network master. In Lon or BACnet, setting an output<br />

to use math functions will automatically activate the VAV Controller’s own math<br />

calculations (even if this was not enabled in the Math Functions configuration<br />

screen). See the Math Functions configuration screen on p.33 for more details.<br />

• Off: The output remains inactive and will not appear on the Home screen.<br />

2.1.5.1 Setpoint Selection*<br />

• Heating Setpoint: The desired setpoint in heating mode. Setpoint cannot be zero.<br />

• Cooling Setpoint: The desired setpoint in cooling mode. Setpoint cannot be zero.<br />

2.1.5.2 Control Mode Selection*<br />

• Proportional Band: In proportional band control, the output is zero when the demand<br />

reaches the setpoint, increases proportionally with the demand by pulsing (Outputs 1<br />

to 4) or modulating (Output 5), and finally reaches 100% when the demand reaches<br />

the setpoint + proportional band (see figure below). The sum of the setpoint and the<br />

demand cannot be greater than 100%.<br />

Proportional Band<br />

0%<br />

Output = 0% Output = 100%<br />

Demand<br />

Setpoint<br />

Figure 2.1.12: Proportion deadband diagram<br />

Ex.: Setpoint = 25%<br />

Proportional band = 50%<br />

Demand = 45%<br />

Output = ((45-25)x100)/50 = 40%<br />

• Differential: In differential mode, the output alternates between 0 and 100% (ON/OFF).<br />

From an OFF state, the output becomes ON when the demand passes (setpoint +<br />

differential/2) and remains ON until the demand goes back down below (setpoint –<br />

differential/2) (see figure below). The setpoint must always be greater then the<br />

differential. The sum of the setpoint and the differential must be less than 100%.<br />

19<br />

www.prolon.net<br />

info@prolon.net

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!