2.1.9 Calibration –> Temperature Calibration<br />
Figure 2.1.17: Temperature calibration configuration screen<br />
• Room Calibration: This value will be added to the temperature received from the room<br />
sensor to calculate the actual room temperature. You can use the slider or simply<br />
type in the desired value.<br />
Units MIN MAX Default<br />
°C -15 +15 0<br />
°F -27 +27 0<br />
• Supply Calibration: This value will be added to the temperature received from the<br />
supply sensor to calculate the actual supply temperature. You can use the slider or<br />
simply type in the desired value. This value will NOT BE ADDED if the network<br />
provides the supply temperature.<br />
Units MIN MAX Default<br />
°C -15 +15 0<br />
°F -27 +27 0<br />