VAV Controller<br />

www.prolon.net<br />

1 VAV Controller Icon<br />

Each VAV Controller added to your system has its own icon. Each icon displays data<br />

about the VAV Controller it represents, and this data is updated regularly. You can open<br />

the configuration screen for a VAV Controller by double-clicking on its icon. If the VAV<br />

Controller is offline, all data values will show “N/A” (not applicable).<br />

Figure 1.1.1: Typical VAV Controller icon<br />

Please note that if the VAV Controller is Pressure Independent, the airflow in the duct<br />

will be shown in the icon. Otherwise, the damper position will be displayed instead.<br />

1.1 Icon Data<br />

• Title: The name of the VAV Controller. You can change it by right clicking the icon and<br />

choosing “Rename”. By default it is set to “<strong>VC1000</strong>”.<br />

• PIN number: This can be seen in the blue and orange circle (yin/yang) at the left side<br />

of the icon. This is the address number you typed when creating the icon. It<br />

represents the PIN number on the dipswitch of the VAV Controller.<br />

• Temperature: The current room temperature. Will display “N/A” if there is no<br />

temperature sensor attached or if offline.<br />

• Setpoints: The active heating and cooling setpoints, respectively. Will display “N/A” if<br />

the VAV Controller is offline.<br />

• Demand: The demand calculated by this VAV Controller. Ranges from 100% cooling to<br />

100% heating. Will display “N/A” if the VAV Controller is offline.<br />

• Damper: The position of the damper in percentage. Will be replaced by “Flow” (airflow<br />

in the duct) if the VAV Controller is pressure independent. Will display “N/A” if the<br />

VAV Controller is offline.<br />

• Flow: The airflow in the duct controlled by this VAV Controller in CFM (cubic feet per<br />

minute). Will be replaced by “Damper” (damper position) if the VAV Controller is<br />

pressure dependent.<br />