VAV Controller<br />

www.prolon.net<br />

• Min Ventilation Heat Setpoint: The minimum airflow that the damper tries to achieve<br />

when heating (overrides minimum ventilation setpoint during heating only). To enable<br />

this setpoint, one of the outputs must be set to “Duct Heater” (see p.20).<br />

Units MIN MAX Default<br />

Cubic feet per<br />

minute (cfm)<br />

0 2000 120<br />

2.1.7.2 Duct Setup<br />

• Duct Diameter: The diameter of the duct in which the flow sensor is installed.<br />

Units MIN MAX Default<br />

Inches 0 20 8<br />

• K Factor: Multiplication factor induced by the airflow sensor (specified by the<br />

manufacturer).<br />

Units MIN MAX Default<br />

N/A 1 300 2.39<br />

• Sensor Type: The type of flow sensor used.<br />

• Low Velocity: Up to 1200 fpm.<br />

• High Velocity: Up to 2200 fpm.<br />

2.1.7.3 Sensitivity<br />

• Sensor Differential: The airflow must change by half of this amount before the damper<br />

will attempt to compensate for the change in airflow.<br />

Units MIN MAX Default<br />

Cubic feet per<br />

minute (cfm)<br />

0 1000 40<br />

• Damper Speed: The speed at which the damper will move to reach the desired airflow.<br />

Slow this down for increased stability. 1=slow, 5=fast (3 is the default).<br />

25<br />