VAV Controller<br />

www.prolon.net<br />

• Proportional:<br />

Units MIN MAX Default<br />

°C 0 10 1<br />

°F 0 18 1.8<br />

• Integral: Defined as the amount of time required to cause the pulse width to vary by<br />

100% to compensate for a continual error of 1 °C.<br />

Units MIN MAX Default<br />

min 0 600 60<br />

2.1.6.4 Setup<br />

• Cycle Length: The amount of time of a total ON AND OFF cycle.<br />

Units MIN MAX Default<br />

min 5 250 15<br />

• Outside Cutoff Temp: Above this temperature, the radiant floor output always<br />

remains deactivated. (There is a 2°C differential to allow for temperature<br />

fluctuations).<br />

Units MIN MAX Default<br />

°C 5 30 15<br />

°F 41 86 59<br />

• Slab Temperature Calibration: This applies an offset to the slab temperature reading,<br />

if required.<br />

Units MIN MAX Default<br />

°C -15 15 0<br />

°F -27 27 0<br />

23<br />

www.prolon.net<br />