VAV Controller<br />
www.prolon.net<br />
• Unoccupied Mode: This option lets you decide if the master should modify the math<br />
calculation strategies during unoccupied mode.<br />
• Max demand: During unoccupied mode, “Averaging” type math functions will<br />
be replaced by “Max demand” type functions:<br />
o “Weighted Average” is replaced by “Max Demand”. In the case<br />
where there are conflicting demands between different slaves<br />
(cooling and heating), heating has priority.<br />
o “Weighted Average (Cooling Only)” is replaced by “Maximum<br />
o<br />
Cooling”<br />
“Weighted Average (Heating Only)” is replaced by “Maximum<br />
Heating”<br />
• Normal: Math functions will always be calculated the same way, regardless<br />
of occupancy.<br />