Fig. 1-53:<br />

Internal PI-Controller Block Diagram<br />

Errorhandling<br />

The function block generates the following error messages<br />

Additional1/Additional2 using the "F_RELATED_TABLE", 16#0170:<br />

in<br />

ErrorID Additional1 Additional2 <strong>Description</strong><br />

INPUT_RANGE_ERROR<br />

(16#0006)<br />

INPUT_RANGE_ERROR<br />

(16#0006)<br />

INPUT_RANGE_ERROR<br />

(16#0006)<br />

INPUT_RANGE_ERROR<br />

(16#0006)<br />

INPUT_RANGE_ERROR<br />

(16#0006)<br />

RESOURCE_ERROR<br />

(16#0003)<br />

RESOURCE_ERROR<br />

(16#0003)<br />

RESOURCE_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

ACCESS_ERROR<br />

(16#0003)<br />

16#0801 16#0001 Selected "ControlledValueIDN" is not supported<br />

16#0801 16#0002 HighLimit < LowLimit<br />

16#0801 16#0003 Input-variable PControl < 0<br />

16#0801 16#0004 Input-variable IControl < 0<br />

16#0801 16#0005 SensorDeadTime < 0<br />

16#0802 16#0000 Selected probe number and edge does not correspond to<br />

the probe configuration (S-0-0169)<br />

16#0803 16#0000 Continuous measurement not active (S-0-0169)<br />

16#0804 16#0000 Probe signal is not configured, or selected probe signal is<br />

not supported<br />

16#0805 16#0001 Required probe value S-0-0130 is not configured in the<br />

optional cyclic AT data of the measured axis<br />

16#0805 16#0002 Required probe value S-0-0131 is not configured in the<br />

optional cyclic AT data of the measured axis<br />

16#0805 16#0003 Required probe value S-0-0132 is not configured in the<br />

optional cyclic AT data of the measured axis<br />

16#0805 16#0004 Required probe value S-0-0133 is not configured in the<br />

optional cyclic AT data of the measured axis<br />

16#0805 16#0005 Required probe value S-0-0409 is not configured in the<br />

optional cyclic AT data of the measured axis<br />

16#0805 16#0006 Required probe value S-0-0410 is not configured in the<br />

optional cyclic AT data of the measured axis<br />

16#0805 16#0007 Required probe value S-0-0411 is not configured in the<br />

optional cyclic AT data of the measured axis<br />

16#0805 16#0008 Required probe value S-0-0412 is not configured in the<br />

optional cyclic AT data of the measured axis<br />

16#0805 16#0009 Required probe value S-0-0405 Bit 0 is not configured in<br />

the signal control word of the measured axis<br />

16#0805 16#000A Required probe value S-0-0406 Bit 0 is not configured in<br />

the signal control word of the measured axis<br />

ACCESS_ERROR 16#0805 16#000B Required parameter S-0-0048 is not configured in the<br />

DOK-<strong>MLD</strong>-S*-<strong>Tech</strong><strong>FB</strong>*****-AW01-EN-D