3.2 Operational Specifications<br />
Range of outputs on channel #1:<br />
Field selectable from the following:<br />
Function Minimum Range Maximum Range<br />
Water vapour 1 20% 0 to 100%<br />
Dew point 1 20°C -50 to 100°C<br />
Absolute humidity 1 200g/Kg 0 to 10,000 g/kg<br />
Mass fraction 1 50g/Kg 0 to 1,000 g/kg<br />
Probe 1 oxygen 1.0% 0.0 to 25.0%<br />
Probe 2 oxygen 1.0% 0.0 to 25.0%<br />
No output<br />
Range of outputs on channel #2:<br />
Field selectable from the following:<br />
Function Minimum Range Maximum Range<br />
Water vapour 2 20% 0 to 100%<br />
Dew point 2 20°C -50 to 100°C<br />
Absolute humidity 2 200g/Kg 0 to 10,000 g/Kg<br />
Mass fraction 2 50g/Kg 0 to 1,000g/kg<br />
Probe 1 oxygen 1.0% 0.0 to 25.0%<br />
Probe 2 oxygen 1.0% 0.0 to 25.0%<br />
No output<br />
Range of local oxygen indication: 1.0 x 10 -30 to 100%<br />
Local display, secondary functions:<br />
Zone 2 water vapour 0 to 100%<br />
Zone 1 dew point -50 to 100°C<br />
Zone 2 dew point -50 to 100°C<br />
Zone 1 absolute humidity<br />
0 to 1,000 kg/Kg<br />
Zone 2 absolute humidity<br />
0 to 1,000 kg/kg<br />
Zone 1 mass fraction<br />
0 to 1,000 g/kg<br />
Zone 2 mass fraction<br />
0 to 1,000 g/kg<br />
Ambient temperature -25 to 80°C<br />
Ambient relative humidity 5 to 95%<br />
Runtime<br />
>10 years (hours and minutes)<br />
Service date<br />
Day/Month/Year<br />
Probe 1 temperature -25 to 1372°C<br />
Probe 2 temperature -25 to 1372°C<br />
Probe 1 EMF<br />
-40 to 1350mV<br />
Probe 2 EMF<br />
-40 to 1350mV<br />
Probe 1 impedance<br />
0.0 to 300.0kohm<br />
Probe 2 impedance<br />
0.0 to 300.0kohm<br />
Probe 1 oxygen 1x10 -30 % to 100%<br />
Probe 2 oxygen 1x10 -30 % to 100%<br />
The top line item can also appear on the secondary line if another item is selected on the top line. This list is<br />
based on zone water vapour being selected for the top line.<br />
January 2012<br />
10 <strong>1735</strong> Water Vapour Transmitter