Liebert Challenger 3000 with iCOM
Liebert Challenger™ 3000 with iCOM Installation Manual - 3 ... - DCES
Liebert Challenger™ 3000 with iCOM Installation Manual - 3 ... - DCES
- No tags were found...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
1.1.3 Split SystemsIntroductionEach air-cooled split system consists of an evaporator section and one of the following condensingunits.Prop Fan Air-CooledProp Fan units include scroll compressor, condenser coil, prop fan, high pressure switch, hot gasbypass and <strong>Liebert</strong> Lee-Temp head pressure control. Unit is designed for outdoor location.Centrifugal Fan Air-CooledCentrifugal Fan units include scroll compressor, condenser coil, centrifugal blower assembly,high-pressure switch, hot gas bypass and <strong>Liebert</strong> Lee-Temp head pressure control. Unit must bemounted indoors. Duct flanges are optional.Water-CooledEach water-cooled split system consists of an evaporator section and a water/glycol condensing unit,which includes scroll compressor, coaxial condenser, water regulating valve, hot gas bypass andhigh-pressure switch. Design pressure is 150 psi (1034 kPa) as standard and 350 psi (2413 kPa) asoptional.Glycol-CooledEach glycol-cooled split system consists of an evaporator section, a water/glycol condensing unit (asdescribed above), a pump package, and a 95°F (35°C) design ambient drycooler.4