Split System ModelsFigure 42 3-ton water/glycol-cooled condensing unit (con't.)Single- orthree-phaseelectric servicenot by <strong>Liebert</strong>Field-supplied unit disconnectswitch when optional disconnectis not provided in unitField-supplied 24V NEC Class 1wiring to fan/coil unitField-supplied 24V NEC Class 1wiring to drycooler(glycol-cooled units only)Line-voltage electricpower supply entranceEarth/ground connectionConnection terminal for field-suppliedearth-grounding wireFactory-wired componentson electric panelOptional factory-installeddisconnect switchLow-voltage electricpower supply entranceRemote drycooler connectionTerminals 70 & 71 suppliedfor connection to remote drycoolerUse field-supplied 24V NEC Class 1wiring (glycol-cooled units only)NOTES1. Refer to specification sheet for full load ampand wire size amp ratings.2. Control voltage wiring must be a minimumof 16 GA (1.6mm) for up to 75' (23m) ornot to exceed 1 volt drop in control line.Heat rejection connection.Field-supplied 24V NEC Class 2 wiring.Wire connections from evaporator mod:1. 24V GND2. 24V supply3. High-pressure alarm (optional)4. Hot gas bypass connection(only on units <strong>with</strong> hot-gas bypass)DPN000209_Rev074